400Nm Fail Safe Electric Actuator
Fail safe smart electric actuator with position setting function when lost input signal
Features
- 90° turn with proportional to input control signal
- Self-calibrating with continuously output position monitoring signal as standard
- All metal gear train with self-locking bronze alloy worm gear
- Watertight IP67 and NEMA 4X aluminum alloy enclosure with 100% underwater tests
- World-leading EMC, 100% passed EFT, ESD and Surge tests
- Stable operation on extra high/low temperature with high humidity
- Full potted resin plastic packaged controller to protect electronics from vibration and moisture
- Fail safe drive to any setting position when input signal loses
- CSA listed/UL complied/CE marked/RoHS 3.0 tested
Specification:
| Name: | Fail Safe Smart Electric Actuator |
| Motor Power: | 6W To 140W |
| Output Signal: | 4-20mADC |
| Standard Time: | 20S To 75S |
| Total Weight: | 1.2KG To 20KG |
| Installation Angle: | 360° |
| Power Supply: | 24VAC/110VAV/220VAC/380VAC |
| Standard Torque: | 50Nm To 2500Nm |
| Input Signal: | 4-20mADC/1-5VDC/2-10VDC |
| Protection Grade: | IP67 NEMA4/4X |
| Ambient Temperature: | -25℃~+55℃ / -13°F~+131°F |
| Feature: | Position Setting Function When Lost Input Signal |
Description
DCL-E modulating type electric actuators are fail-safe. When control signal loses or mistaken input beyond certain range(4-20mA/2-10V), and power is still on, actuator can drive valve to any position that has been set before, such as full open or full close position. Self-locking function can also prevent back driving and hunting when power lose. These functions can keep whole control system safe when malfunction happens.
All actuators are rigorous tested and certified by CSA per UL and CSA standard, tested by SGS per CE and RoHS 3 standard. The self-designed high stability control packs are also certified and tested by top companies to ensure no problems during high humidity and high temperature.
| Type | DCL-05E | DCL-10E | DCL-20E | DCL-40E | DCL-60E | DCL-100E | DCL-160E | DCL-250E |
| Power | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC110/220 | AC110/220 | AC110/220 |
| Output Torque | 50Nm | 100Nm | 200Nm | 400Nm | 600Nm | 1000Nm | 1600Nm | 2500Nm |
| Acting Time | 20S | 30S | 30S | 30S | 45S | 30S | 48S | 75S |
| Turning Angle | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° |
| Motor Power | 10W | 25W | 40W | 90W | 90W | 120W | 140W | 140W |
| Rated Current | 1.50/0.24/ 0.16A | 2.12/0.57/ 0.35A | 3.65/0.65/ 0.37A | 6.80/1.12/ 0.57A | 6.80/1.18/ 0.60A | 1.93/0.94A | 1.75/0.96A | 1.75/0.98A |
| Total Weight | 2.5kg | 4.5kg | 9kg | 9.5kg | 10kg | 19kg | 19.5kg | 20kg |
| Input Signal | 4-20mADC,1-5VDC,2-10VDC | |||||||
| Output Singal | 4-20mADC | |||||||
| Basic Error | not more than ±1% | |||||||
| Reciprocating Error | not more than 1% | |||||||
| Dead Space | 0.5%-5.0% adjustable | |||||||
| Damping Characteristic | 0 times | |||||||
| Repeating Error in Actuator | ≤1% | |||||||
| Insulating Resistance | AC24V:100MΩ/250VDC AC110/220V:100MΩ/500VDC | |||||||
| Withstand Voltage Class | AC24V:500VAC 1minute AC110/220V:1500VAC 1minute | |||||||
| Protection Class | IP67 | |||||||
| Installation Angle | 360°at any angle | |||||||
| Electric Interface | Two G1/2 Wate-proof Cable Connectors,one for power line and one for signal line | |||||||
| Ambient Temperature | -20℃~+55℃ | |||||||
| Optional Function | Over-torque protector/Dehumidify Heater/Passive contact switch/Dome indicator/Handle | |||||||
| Remark | Any other input or output signal needed, please specified in purchase order. | |||||||
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.