50W And 500W Horizontal And Vertical Flammability Testing Equipment

 

Standard:

IEC60695-11-3 ‘Fire hazard testing – Part 11-3: Test flames – 500 W flames – Apparatus and confirmational test Methods’;

IEC60695-11-4 ‘Fire hazard testing – Part 11-4: Test flames – 50 W flames – Apparatus and confirmational test Methods’;

IEC60695-11-10 ‘Fire hazard testing – Part 11-10: Test flames – 50 W horizontal and vertical flame test methods’;

IEC60695-11-20 ‘Fire hazard testing – Part 11-20: Test flames – 500W flame test method’.

 

Application:

This horizontal and vertical flame test apparatus is intended to compare the burning behaviour of different materials used in electrotechnical products when vertically or horizontally oriented test bar specimens are exposed to a small flame ignition source with a nominal thermal power of 50 W and 500 W.

 

Test items:

50W Horizontal burning test;

50W Vertical burning test;

500W Horizontal burning test;

500W Vertical burning test. Flammability Testing Equipment

Horizontal burning test is intended to determine the linear burning rate of materials under specific test conditions. Vertical burning test is intended to determine whether materials self-extinguish under specific test conditions.

 

Fire tests made on a material under the conditions specified can be of considerable value when comparing the relative burning behaviour of different materials, controlling manufacturing processes or assessing any change in burning characteristics. The results obtained from these fire test methods are dependent on the shape and orientation of the test specimen, on the environment surrounding the test specimen, and on the conditions of ignition.

The significant feature of these fire test methods is the arrangement of the test specimens in either a horizontal or a vertical position. These testing arrangements make it possible to distinguish between different classes of material flammability.

 

Parameter:

Flame power 50W 500W
Conforming to standards UL94, IEC60695-11-4 UL94, IEC60695-11-3
Timing device 9999×0.1s 9999×0.1s
Combustion angle 0°, 20°, 45° 0°, 20°, 45°
Gas pressure 0.1 MPa 0.1 MPa
Height of flame Total height 20±2mm Inner flame 40±2mm total height 125
Distance for temperature measurement 10±1mm 55±1mm
Standard for blast burner IEC60698-11-4, UL94 IEC60695-11-3, UL94
Temperature testing Max. 1100℃, thermocouple: type K Max. 1100℃, thermocouple: type K
Gas flow rate 105 ml/min±5 ml/min 965 ml/min±30 ml/min
Water column height <10mm 125mm±5mm
Temperature rise time From 100℃±5℃ to 700℃±3℃ is 44s±2s From 100℃±5℃ to 700℃±3℃ is 54s±2s
Accuracy of flow rate 1% 1%
Weight of copper block

Ф5.5mm,

1.76 g±0.01 g

(before drilling)

Ф9mm,

10g±0.05 g

(before drilling)

Type of gas Methane or coal gas Methane or coal gas
Volume of chamber 0.75m³, black inner gas
Using environment

15 °C to 35 °C temperature,

45 % to 75 % relative humidity

Flammability Testing Equipment

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company HJ AUTOMATIC CONTROL TECHNOLOGY CO., LTD
Location No.6-36, Yaogu Farm, Shibi No.3 Village, Shibi Street, Panyu District, Guangzhou, Guangdong, China
Contact Person Tessa Huang

Request A Quote

Please check your email address.
Your message must be at least 20 characters.