Automatic Foam Extinguishing Agent Freezing Point Tester Double Holes GB 15308
| Attribute | Value |
|---|---|
| Human computer interface | 7-inch color LCD touch screen |
| Number of test holes | double holes |
| Temperature range | +30 ℃ ~ -80 ℃ or +30 ℃ ~ -70 ℃ |
| Display accuracy | 0.1℃ |
| Printer | Small thermal printer |
| Result output | Can be equipped with USB drive output |
SH15308 Full-automatic foam extinguishing agent setting point meter
SH15308 foam extinguishing agent freezing point meter is designed and manufactured according to the requirements of GB15308 foam extinguishing agent freezing point, and is applicable to determining the freezing point of foam extinguishing agent according to the methods specified in the above standards. The full-automatic freezing point tester adopts modern advanced technology and integrates mechanical, electronic and microcomputer technology, which can automatically complete the freezing point test of foam extinguishing agent.
Compliant with standard: GB 17835-2024 water-based fire extinguishing agent
- Compliant with standards: GB 15308 GB 17835
- Human computer interface: 7-inch color LCD touch screen
- Refrigeration method: Fully enclosed high-efficiency refrigeration compressor
- Detection method: The device automatically records the temperature time curve
- Can store historical data for easy retrieval; Simultaneously equipped with USB output function
- Data extension: can export test curves
- Standard micro printer with automatic measurement and printing
- Standard micro printer with automatic measurement and thermal printing
- Number of test holes: double holes
- Temperature range: +30 ℃ ~ -80 ℃ or +30 ℃ ~ -70 ℃
- Display accuracy: 0.1 ℃
- Quantity: Place the test tube at a liquid level of approximately 50mm
- Refrigeration medium: metal bath refrigeration
- Printer: Small thermal printer
- Storage method: The experimental results can store 1999 sets of historical data for easy retrieval
- Result output: It can also be equipped with a USB drive output function to output to the PC for long-term storage
- Output format: The output format of the result USB drive is CSV or Excel
- Standard printing: Standard micro printer with automatic measurement and thermal printing
- Instrument size: 650 * 480 * 620mm
- Instrument weight: 75kg
- Packaging size: 690 * 520 * 660
- Packaging weight: 80kg
| Number | Name | Quantity | Unit | Note |
|---|---|---|---|---|
| 1 | Host | 1 | Unit | |
| 2 | Condensation temperature glass test tube | 2 | Set | |
| 3 | Condensation point temperature sensor | 2 | Set | |
| 4 | Power line | 1 | Strip | |
| 5 | Fuse tube | 1 | Piece | |
| 6 | Operation instructions | 1 | Copy | |
| 7 | Packing list | 1 | Copy | |
| 8 | Certificate of Conformity Warranty Card | 1 | Copy |
Get in Touch