ELTEK Flatpack S 48V/1000W SHE 241122.106 Rectifier Module
ELTEK Flatpack S 48V/1000W SHE 241122.106 rectifier module
Product Description:
The Flatpack S rectifiers incorporate Telecom specifications, high efficiency, ORing protection on output and high power in a small, 217 mm deep box.Future proof solution with minimum losses and demand for cooling can be realized using this rectifier and it’s super high efficiency of 97%.The Flatpack S 48/1000 SHE fits in the existing 1U or 2U Flatpack S power cores including Smartpack S controller, battery and load distributions, covering 2 to 5kW applications using a minimum of space, less than 6 and 12 liters, and super low heat dissipation.
| Model | 48/1000 SHE |
| Part number | 241122.106 |
| Input data | |
| Voltage (nominal) | 185 - 250 VAC |
| Voltage (operating range) | 85 - 275 VAC |
| Current (maximum) @ nominal input, full load | 5.9 ARMS |
| Frequency | 45 - 66 Hz |
| Power Factor | > 0.99 at full load |
| Protection | Fuse in L & N, Shutdown when input voltage is out of operating range |
| Output data | |
| Voltage (default) | 53.5 VDC |
| Voltage (adjustable range) | 42 - 57.6 VDC |
| Power (maximum) @ nominal input | 1000 W |
| Power @ 85 VAC | 420 W |
| Current (maximum) @ nominal input | 20.9 A (@VOUT < 48VDC) |
| Hold up time, 950W output power | >10ms; output voltage > 40 VDC |
| Current sharing (10 - 100% load) | ±5% of maximum current from 10 to 100% load |
| Static Voltage regulation (10 - 100% load) |
±0.5% |
| Dynamic Voltage regulation | ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms |
| Ripple | < 150 mVPP , 30 MHz bandwidth |
| Protection | ORing FET, Short circuit proof, High temperature protection, Over voltage Shutdown |
| Other specifications | |
| Efficiency | > 97% |
| Isolation | 4.0 kVDC - input to output, 2.5 kVDC - input to earth, 710 VDC - output to earth |
|
Alarms: Single LED = Red |
Low / high input voltage shutdown, High / low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low output voltage alarm, CAN bus failure |
|
Warnings: Single LED = Yellow |
Rectifier in power de-rate mode, Remote output current limit activated, Input voltage out of range, flashing at overvoltage, Loss of CAN communication with controller |
| Normal operation: Single LED = Green | |
| Operating temp. (5-95% RH n.cond. hum.) |
-40 to + 85°C [-40 to +185°F] |
|
Max output power de-rates above temp / to |
55°C [113°F] / 400W @ 85°C[185°F] |
| Dimensions[WxHxD] / Weight | 72 x 41.5 x 217mm (2.83 x 1.63 x 8.54”) / 620 g ( 1.37 lbs) |
| Design standards | |
| Electrical safety | EN IEC 62368-1:2020/A11:2020, IEC 62368-1:2018, UL 62368-1:2021 C22.2 No. 62368-1:2021, IEC 60950-1:2013 |
|
EMC |
EN IEC 61000-6-1:2019, -6-2:2019, -6-3:2021, -6-4:2019, -6-5: 2015 FCC CFR 47 Part 15:2020, ETSI EN 300 386:v2.2.1, DNV-CG-0339:2021 IEC 62236-4:2018, -5:2018, EN 50121-4:2016+A1:2019, -5:2017+A1:2019 |
| Marine | DNVGL-CG-0339 |
|
Environment |
ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised EU 2015/863 (RoHS), 2012/19/EU (WEEE), IEC 63000:2018 |
Product Details: