ELTEK Flatpack S 36V/1000W HE UI 241122.235 Rectifier Module
ELTEK Flatpack S 36V/1000W HE UI 241122.235 rectifier module
Product Description:
ELTEK Flatpack S 36V/1000W HE UI 241122.235 rectifier module is used in the 3U rack with Smartpack S controller, the Flatpack S rectifiers cover 2 to 8kW applications using a minimum of space, less than 18 liters, and low heat dissipation.
|
Model |
36/1000 HE UI |
|
Part number |
241122.235 |
|
INPUT DATA |
|
|
Voltage (nominal) |
185 - 400 VDC / 185 - 275 VAC |
|
Voltage (operating range) |
85 - 400 VDC / 85 - 305 VAC |
|
Frequency |
DC, 16 2/3 Hz, 45 - 66 Hz |
|
Current (maximum) |
5.9 ADC / 5.9 ARMS |
|
Protection |
Fuse in Positive & Negative, Reversed polarity insensitive, Shutdown above 420 VDC / 305 VAC |
|
OUTPUT DATA |
|
|
Voltage |
40 VDC |
|
Voltage (adjustable range) |
331) - 45 VDC |
|
Power (maximum) @ nominal input |
1000 W / 450 W @16 2/3 Hz input |
|
Power (maximum) @ 85 VDC / 85 VAC input |
440 W / 440 W |
|
Current (max cont.) @ nominal input |
27.8 A (@VOUT < 36 VDC) |
|
Hold up time, maximum output power |
>10ms; output voltage > 33 VDC |
|
Current sharing (10 - 100% load) |
±5% of maximum current from 10 to 100% load |
|
Static Voltage regulation (10 - 100% load) |
±0.5% |
|
Dynamic Voltage regulation |
±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms |
|
Ripple |
< 150 mVPP , 30 MHz bandwidth |
|
Protection |
ORing FET Short circuit proof High temperature protection Over voltage Shutdown |
|
OTHER SPECIFICATIONS |
|
|
Efficiency |
> 95 % |
|
Isolation |
4.2 kVDC - input to output 2.25 kVDC - input to earth 710 VDC - output to earth |
|
Alarms: Red LED |
Low and high input voltage, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure when fan stops, Low output voltage alarm, CAN bus failure |
|
Warnings: Yellow LED |
Rectifier in power de-rate mode, Remote output current limit activated, Input voltage out of range, flashing at overvoltage, Loss of CAN communication with controller |
|
Normal operation: Green LED |
|
|
Alarm relay (NO - opens when de-energized) |
Opens on Alarms and missing input voltage. |
|
MTBF (Telcordia Issue 3 & Method II Case L1) |
>2 700 000 (@ Tambient : 25 °C) |
|
Operating temperature (5-95% RH n.cond. hum.) Maximum output power de-rates above temp / to |
-40 to + 85°C [-40 to +185°F] 45°C [140°F] / 400W @ 85°C [185°F] |
|
Storage temperature |
-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing |
|
Dimensions[WxHxD] / Weight |
72 x 40 x 217mm2) (2.84 x 1.57 x 8.54”)2) / < 850 g (1.9 lbs) |
|
DESIGN STANDARDS |
|
|
Electrical safety |
EN 60950-1:2006+A11:2009+A1:2010+A12:2011 |
|
EMC |
EN 61000-6-1:2007, -6-2:2005, - 6-3:2007 + A1:2010, - 6-4:2007 + A1:2010 EN 50121-1:2015, -2:2015, -4:2015, -5:2015 |
|
Environment |
ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2) RoHS (2011/65/EU) and WEEE (2012/19/EU) compliant |
Product Details:
If you are interested, please let us know the specific model. We will provide the best service and the best price!
Pr
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.