ELTEK Flatpack2 48/3200 HE Solar 241119.650 Rectifier Module
ELTEK Flatpack2 48/3200 HE Solar 241119.650 rectifier module
Product Description:
With the MPPT algorithm ensuring close to 100% panel utilization and an efficiency above 97%, the galvanic isolated solar charger sets new standards for renewable power in telecom.
The combination of innovative design, efficiency and reliability makes the Flatpack2 HE SOLAR stand out.
|
Model |
48/3200 HE SOLAR |
|
Part number |
241119.650 |
|
INPUT DATA |
|
|
Voltage (MPPT range)1) |
100 - 380 VDC |
|
Voltage (operating range) |
85 - 430 VDC |
|
Voltage (start-up) |
150 VDC |
|
Maximum current |
20.3 ADC |
|
Protection |
Fuse, varistor for transient protection, reversed polarity, shutdown when VIN is too low, earth fault check during start-up |
|
OUTPUT DATA |
|
|
Voltage (default) |
53.5 VDC |
|
Voltage (adjustable range) |
422) - 57.6 VDC |
|
Max power, VIN ≥ 170 VDC |
3200 W |
|
Max power, de-rated @VIN = 85 VDC |
1500 W |
|
Max current, @VOUT = 48 VDC |
66.7 A |
|
Current sharing |
Passive to optimize power available from each string of solar panels |
|
Static voltage regulation (10-100% load) |
±0.5% from 10 - 100% load and supplied power not limited by PV panels |
|
Dynamic voltage regulation |
±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms |
|
Ripple |
< 250 mVPP , 30 MHz bandwidth |
|
Protection |
Fuse, Overvoltage shutdown, short circuit proof, high temperature, hot plug-in inrush current limiting |
|
OTHER SPECIFICATIONS |
|
|
Peak Efficiency |
97 % |
|
Isolation |
4.2 kVDC – input and output, 2.5 kVDC – input earth, 0.5 kVDC – output earth |
|
Alarms (Red LED) |
High and low temperature shutdown, Converter Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure |
|
Warnings (Yellow LED) |
Low input voltage, Converter in power derate mode, Remote current limit activated, Input voltage out of range, flashing at overvoltage |
|
Normal (Green LED) |
Input and output ok |
|
MTBF (Telcordia SR-332 Iss.3 Method II Case L1) |
1 440 000 (@ Tambient : 25°C) |
|
Operating temperature (5 - 95% RH non-cond.) |
-40 - 75°C [-40 - 167°F ] |
|
Max output power de-rates above temp / to |
45°C [+113°F] / 2400 W |
|
Storage temperature |
-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing |
|
Dimensions[WxHxD] / Weight |
109 x 41.0 x 327mm [4.25 x 1.61 x 13”] / < 2 kg [4.4lbs] |
|
DESIGN STANDARDS |
|
|
Electrical safety |
IEC/EN 62109-1:2010/-2:2011, EN 62368-1:2020+A11:2020, IEC 62368-1:2018 UL 62368-1:2019, IEC 60950-1:2013 |
|
EMC |
EN 61000-6-1:2016, -6-2:2016, -6-3:2007 + A1:2011, -6-4:2007 + A1:2011, IEC 61000-6-5:2015, EN 300 386:v2.1.1, FCC CFR 47 Part 15:2013 |
|
Environment |
ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) 2011/65/EU (RoHS) & 2012/19/EU (WEEE) Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised |
Product Details:
If you are interested, please let us know the specific model. We will provide the best service and the best price!
Pr
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.