PD Free AC Transformer Test Systems, HV Type High Potential Test Equipment
PD Free AC Transformer Test Systems , PD Free HV Type Test Transformer Voltage Withstand System
I. Products Description and Application :
CQSB series PD free power frequency test transformer system is mainly used for power frequency voltage withstand for electrician products and insulation materials or insulation structure. It is also be used for PD free power frequency test power supply of testing objects such as transformer, mutual induction, arrester,etc. it is be used widely in electrician manufacturing department, power operation department, R&D institution and institution of higher learning.The voltage divider of the system has coupling terminal of PD signal , through equipped with 2 or 4 channels PD analyzer (optional), PD detecting for test object can be realized.
The model CQSB-500KVA/500KV has two stackable cylinder type Test Transformer in series connection to output 500KV test voltage and 1A test current. The duty cycle is 60mints on ,60mints off ,
Until now , this test set had formed many different serialized model according to different votage withstand test applications .The alike model can see other typical model at the following clause.
II. Main Components:
- Power frequency intelligent measurement and control system or console type control cabinet,
- Power supply switch cabinet,
- Voltage regulator cabinet,
- Testing transformer with iron tank type or cylinder type,
- Compensating reactor,
- Power frequency protective resistance,
- Electronic rapid protective device
- Coupling capacitive voltage divider.
For example Model CQSB-500KVA/500KV
| SN | Name of Components | Type and specification | Qty. | Each weight | Each Dimension |
| 1 | Control console | FKGB-500KVA | 1piece | 180kgs | 1200*420*820mm |
| 2 | Electric voltage regulator cabinet | DT-500KVA | 1piece | 2500kgs | 1100*1050*1250mm |
| 3.1 | First stackable cylinder type Test Transformer | CQSB-500KVA/250KV | 1piece | 3000kgs | D1200*H2800mm |
| 3.2 | Second stackable cylinder type Test Transformer | CQSB-250KVA/250KV | 1piece | 2400kgs | D1200*H2500mm |
| 4 | Protection resistance | BHR-1A/500KV | 1pieces | 120kgs | D380*L850mm |
| 5 | Voltage divider with coupling capacitance | TJF-500KV/500pF | 1set | 200kgs | D320*H6000mm |
| 6 | Special test accessories | ||||
| Note : Special requirement can be made by order. | |||||
III. Applicable objects
- Partial discharging and AC voltage withstand test for HV electrical engineering and apparatus, such as transformer, GIS, mutual inductor,switch,bushing,arrester,cables.
- Power AC voltage withstand of insulation materials
IV. Technical features
- Little magnitude of complete installation which can guarantee the magnitude within 5pC(except for special cases)
- Expoxy resin poured shell,glass fiber convolved non corona high voltage insulation outer barrel
- Low impedance of complete equipment, complete functions of over voltage,over current, arc protection with reliability
- Dedicated mould processed for grading shield,aluminium molded, smooth surface,light weight, convenient for installation
- The large capacity HV test device employs power frequency intelligent measurement and control system to ensure much higher intelligence and
- automation of controlling and protection.
- Sampling and using optical communication, thoroughly isolate high voltage and low voltage control loop.
- Self-inspection and display of real-time status are available in the testing processing.
- Perfect management function of data and report.
- Being able to record and draw HV U/T,I/T testing curve
V. Test connection figure (For example: model CQSB-500KVA/500KV):
VI. Advantages
- Pure power frequency test at 50Hz or 60Hz, output voltage distortion (THD) is very small.
- Meet low partial discharge measurement requirements
- Modular structure for saving space in the test hall
- Low impedance, wide application range
- Easy to operate with computer controlled measurement system
- Complete protection circuit to ensure the safety of personnel and equipment
- Surge and transient protection sensitive electronic components
- Particularly suited for tests requiring stable voltage even if the load changes under voltage (corona, wet & pollution tests) or when the load is inductive (inductive voltage transformers).
VII. General Technical data:
- Mode of system test: PD Free AC Withstand Voltage Test Systems With Cylinder Type Transformer
- System model : CQSB-500KVA/500KV
- Input power supply : 380±10%(single-phase),50Hz/60Hz
- Rated output capacity: 500kVA
- Rated output Voltage: 500KV
- Max Test voltage : no more than 500KV
- Rated output current: 1.0A
- Reg. Freq range : 50/60Hz
- Output voltage waveform: pure sine wave
- Temperature rise: Less than 65K under rated current working 60mints;
- Noise level: No more than 65dB
- Structure: oil-immersed with cylinder type designed
VIII. Other optional components
- Power supply noise filter
- Triple and fifth filter
- Compensating reactor
- Over-voltage electronic fast protection device
- SF6 standard capacitor·
- Partial discharge detector
IX. Other Typical Model
1.Single transformer type :
| MODEL |
Rated capacity (KVA) |
LV input supply(KV) | Rated output voltage(KV) |
Cylinder transformer dimension D× H(mm) |
Weight (kg) |
| CQSB-1.5KVA/50KV | 1.5 | 0.22 | 50 | φ430*580 | 65 |
| CQSB-2.5KVA/50KV | 2.5 | 0.22 | 50 | φ280*500 | 70 |
| CQSB-3KVA/50KV | 3 | 0.22 | 50 | φ300*510 | 72 |
| CQSB-5KVA/50KV | 5 | 0.22 | 50 | φ460*580 | 110 |
| CQSB-5KVA/100KV | 5 | 0.22 | 100 | φ640*820 | 130 |
| CQSB-10KVA/100KV | 10 | 0.22 | 100 | φ620*850 | 160 |
| CQSB-50KVA/100KV | 50 | 0.4 | 100 | φ725*1100 | 500 |
| CQSB-12KVA/120KV | 12 | 0.38 | 120 | φ750*1230 | 380 |
| CQSB-15KVA/150KV | 15 | 0.38 | 150 | φ820*1220 | 500 |
| CQSB-20KVA/200KV | 20 | 0.38 | 200 | φ1080*1700 | 900 |
| CQSB-50KVA/250KV | 50 | 0.38 | 250 | φ1460*1520 | 1250 |
| CQSB-75KVA/250KV | 75 | 0.38 | 250 | φ1460*1780 | 1450 |
| CQSB-75KVA/500KV | 75 | 0.38 | 500 | φ2000*4850 | 6800 |
| CQSB-100KVA/100KV | 100 | 0.38 | 100 | φ1000*1250 | 800 |
| CQSB-100KVA/150KV | 100 | 0.38 | 150 | φ1410*1620 | 1700 |
| CQSB-100KVA/250KV | 100 | 0.6 | 250 | φ1100*1450 | 1550 |
| CQSB-125KVA/250KV | 125 | 0.38 | 250 | φ1540*2060 | 3460 |
| CQSB-150KVA/150KV | 150 | 0.6 | 150 | φ1420*1620 | 2200 |
| CQSB-2000KVA/500KV | 2000 | 3 | 500 | φ3000*4800 | 50000 |
2.Stackable cylinder transformers type:
| MODEL |
Rated capacity (KVA) |
LV input supply(KV) | Rated output voltage(KV) |
Cylinder transformer dimension D× H(mm) |
Weight (kg) |
| CQSB-10KVA/2*50KV | 10 | 0.2 | 100 | φ410*980 | 200 |
| CQSB-25KVA/2*125KV | 25 | 0.38 | 250 | φ1250*2200 | 890 |
| CQSB-100KVA/2*200KV | 100 | 0.38 | 400 | φ1580*3650 | 2500 |
| CQSB-150KVA/2*150KV | 150 | 0.38 | 300 | φ1600*3200 | 3980 |
| CQSB-300KVA/2*150KV | 300 | 0.38 | 300 | φ1600*3800 | 4280 |
| CQSB-250KVA/2*250KV | 250 | 0.38 | 500 | φ2220*6100 | 11200 |
| CQSB-500KVA/2*250KV | 500 | 0.6 | 500 | φ2030*4600 | 18500 |
| CQSB-600KVA/2*300KV | 600 | 3 | 600 | φ3200*8000 | 19000 |
| CQSB-1200KVA/2*300KV | 1200 | 0.6 | 600 | φ3000*6200 | 28900 |
| CQSB-1250KVA/2*125KV | 1250 | 3 | 250 | φ4500*3200 | 14500 |
| CQSB-300KVA/2*300KV | 300 | 3 | 600 | φ2610*5600 | 10000 |
Get in Touch