FP300 Addressable Fire Alarm Panel - 324 Point Capacity, 4.3" Color Display, EN 54-2 Compliant

Price Negotiable
Price: USD 600 - 750 / set
MOQ: 1
Delivery Time: 1-10 work days
Brand: HiYi
Product Description
FP300 Addressable Fire Alarm Control Panel

LPCB Approved intelligent addressable fire alarm system with advanced monitoring and control capabilities for comprehensive fire protection.

FP300 Addressable Fire Alarm Control Panel front view showing 4.3-inch color display and control interface
System Overview

The FP300 Fire Alarm Control Panel (FACP) monitors input signals, provides clear indications, and activates programmed outputs in response to fire detection events. Designed for compliance with EN 54-2 standards, this system offers straightforward installation, operation, and maintenance procedures.

Key Features & Benefits
  • Supports up to 324 addressable points on a single loop with expansion capabilities
  • 4.3-inch color LCD display with 480×272 resolution for clear system status monitoring
  • 32-zone indication and control panel for rapid location identification during alarms
  • Comprehensive event logging with 1000 historical records for fire, fault, and operation events
  • Independent programmable conventional sounder circuit output
  • Integrated power supply with battery backup system
  • Built-in printer for system reports and event documentation
  • Flexible cause and effect programming via front panel interface
  • Advanced testing capabilities including zone test, point test, and module start/stop functions
  • USB interface for convenient configuration loading and historical data management
  • Three-level hierarchy management system with key lock anti-tamper protection
  • CAN bus supports interconnection of up to 20 FACPs and RS485 for up to 30 fire indicating panels per FACP
FP300 Addressable Fire Alarm Control Panel internal components and wiring diagram
Application Scope

Ideal for office buildings and commercial facilities requiring reliable fire detection systems. The FP300 provides effective fire prevention and early warning capabilities to protect property and ensure occupant safety.

Technical Specifications
Parameter Specification
Mains Supply 230VAC (-15%, +10%), 47-63Hz, Max current 0.8A
Mains Fuse T3.15AL250V
Operating Voltage 18.5-30V
Recommended Mains Cable Screened or standard/black mains cable, cable size 0.75mm²
Power Rating Imax.a=1.2A; Imax.b=2.6A; Imin=0.65A
Max. Charging Current 1.2A
Max. Internal Resistance of Battery 1.5Ω
Battery Fuse F8AL250V
Quiescent Current (full loaded) < 0.4A

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Beijing HiYi Technology Co., Ltd
Location Room 1302,Yufei Building, 42 Dongzhimenwai Street, Dongcheng District, Postcode:100027 Beijing,China
Contact Person Lisa Niu

Request A Quote

Please check your email address.
Your message must be at least 20 characters.