General
MNS LV withdrawable switchgear is manufactured by standard module through consulting MNS series low voltage switch cabinet of Switzerland ABB Company and synthetically improved. The device is applicable to the system with AC 50Hz, rated working voltage 660V and below, used as a control device for various power generation, transmission, distribution, power transfer, and power consumption devices. It is widely used in low voltage distribution systems of the various mining enterprises, tall buildings, and hotels, municipal construction, etc. Besides the general land use, after special disposal, it also can be used for marine petrol drill taken platform and nuclear power station. The device accords with international standard IEC439-1 and national standard GB7251.1.
Technical Data
| No. | Item | Unit | Data |
| 1 | Rated voltage | V | 660 |
| 2 | Rated insulation voltage | V | 660,1000 |
| 3 | Rated current | A | 1250,2000,2500,3200,4000 |
| 4 | Rated current of drawer accessories | A | 250,400,630 |
| 5 | Max Capacity of Motor | Kw | 320KW |
| 6 | Rated peak with standard current | KA | 105KA,176 KA (0.1S) |
| 7 | Insulation: Power frequency withstand voltage | V | 2500V |
| 8 | Protection class | IP40 | |
| 10 | Overall dimension(Width*Depth*Height) | MM | 600(800,1000)x800(1000)x2200 |
| 11 | Weight | KG | 300~1000 |
Using environment
- The ambient air temperature is not higher than +40℃, not lower than -5℃, and its average temperature within 24h is not higher than +35℃.
- Atmospheric conditions, clean air, relative humidity does not exceed 50% when the highest temperature is +40℃, higher relative humidity is allowed at lower temperatures, for example 90% at +20℃, but temperature changes should be taken into consideration , It is possible to occasionally produce moderate condensation.
- The altitude does not exceed 2000m.
- This device is suitable for the following temperature transportation and storage process: between -25 and +55 ℃, in a short time (not more than 24h) up to +70 ℃, the device should not be subjected to any irreversible recovery at this extreme temperature It should be able to work normally under normal conditions.