12KV RMU SF6 Load Switch Gas Insulated Switchgear HXGN15
SF6 RMU HXGN15 Load Switch Module 12KV GIS GB ISO IEC
Product Introduction
General
The load switch for the power supply cabinet is generally called C module, which is generally used in high-voltage three-phase five-wire cabinets.
Load switch unit which called C-unit included bus-bar, three-station load/earth switch, three-station single spring operating mechanism, there are two independent load switch and ground, switch operation hole, load switch and earthing switch position indication, indicates the kiln voltage indicator of the casing, etc.
Service environment
- Air temperature: -35℃~+40℃
- Humidity: Monthly average 95%; Daily average 90%.
- Altitude:≤ 1000m (Up to 5000 m can be custom)
- Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.
- No frequent violent shake
Technical Data
| No. | Item | Unit | Parameter | |||
| 1 | Rated voltage | kV | 12 | 24 | 36 | |
| 2 | Rated frequency | Hz | 50/60 | |||
| 3 | Rated current | A | 630(1250*) | |||
| 4 |
1min Power frequency withstand voltage |
wet | kV | 38 | 50 | 70 |
| dry | kV | 48 | 60 | 85 | ||
| 5 | Lightning impulse withstand voltage | kV | 75 | 125/150 | 170 | |
| 6 | Rated short circuit breaking current (peak) | kA | 80 | 63 | 63 | |
| 7 | Rated active load and close circuit breaking current | A | 63 | 50 | 50 | |
| 8 | Rated transferring current | A | 1700 | 1200 | 1200 | |
| 9 | Rated short circuit making a current (peak) | kA | 80 | 63 | 63 | |
| 10 | Rated cable(line) charging breaking current | A |
50 and 10 50/10 |
|||
| 11 | Cable charge breaking current in earthing fault | A | 20 | 20 | 20 | |
| 12 | Rated withstand current (peak) | kA | 80 | 63 | 63 | |
| 13 | Short-time withstand current (2s) | kA | 25 | 20 | 20 | |
| 14 | Mechanism life | times | 5000 | 2000 | 2000 | |
Note: For short circuit breaking and the peak current is based on Fuse plus combination
Optional components:
Electric operating-AC 220/110V; DC 24/48/110/220V
Auxiliary contact 5 NO 5 NC
Full set of fuse
FTU communication interface