630A Electric Medium Voltage Switchgear 3 Phase IEC60298
MOQ:
1
Delivery Time:
15 working days
Brand:
KNKONG
Product Description
IEC ISO GB 40.5KV outdoor/indoor medium voltage electric switchgear KYN61
KYN61-40.5KV switchgear,
Knkong/ABB/Schneider VCB
40.5KV, 3-phase, AC 50/60Hz
Standards GB ISO IEC
Knkong/ABB/Schneider VCB
40.5KV, 3-phase, AC 50/60Hz
Standards GB ISO IEC
Product Introduction
The KYN61 medium voltage switchgear manufactured by our company (KNKONG-ELECTRIC) is GB3906 "3-35kV AC metal sealed switchgear", GB / TII022 "Standard common technical requirements for high voltage switchgear and control equipment", DL / T404 " It is compliant with "AC high". Technical conditions for ordering voltage switchgear, IEC60298, "AC metal closed switchgear and control equipment with rated voltage above 1 kV and below 52 kV".
Using environment:
◆ Ambient temperature: upper limit +40°C; and the average value measured within 24 hours does not exceed 35°C, and the lower limit is -10°C.
◆ The altitude does not exceed 1000m
◆ Relative humidity: daily average value does not exceed 95%. The monthly average does not exceed 90%.
◆ Earthquake intensity: no more than 8 degrees.
◆ Water vapor pressure: The daily average value does not exceed 2.2kPa, and the monthly average value does not exceed 1.8kPa.
◆ Ambient environment: a place free from fire, explosion, serious pollution, chemical corrosion and severe vibration
Technical data
| Items | Unit | Data | |
| Voltage | KV | 40.5 | |
| Frequency | Hz | 50 | |
| Current | A | 1250,1600,2000 | |
| Short-circuit Breaking Current | KA | 25,31.5 | |
| Making Current (Peak) | KA | 63,80 | |
| 4s Thermal Stability Current | KA | 25,31.5 | |
| Dynamic Current (Peak) | KA | 63,80 | |
| Insulation Level | 1min Power Frequency Withstand Voltage (r.m.s) | KV | 95 |
| Lightning Impulse Withstand Voltage (Peak) | KV | 185 | |
| 1min Power Frequency Voltage Across the open gap (r.m.s) | KV | 118 | |
| Lightning Impulse Withstand Voltage Across the open gap (Peak) | KV | 215 | |
| Enclosure Protection Class |
Enclosure IP4X, Between Compartments IP2X |
||
| Enclosure Dimension (Width*Depth*Height) | mm | 1400*2800*2600 1600*2800*2600 |
|
| Type of Circuit Breaker | VCB: ZN85-40.5 SF6 Circuit Breaker |
||
*Note: order switchgear should provide SLD(Single-line diagram) by customer
Main components characteristics:
VS1-40.5 Indoor Vacuum Circuit Breaker
Rating voltage: 40.5kV
Rating current: 630 1250 1600 2000 2500A
Rating short circuit breaking current: 20 25 31.5KA
Mechanical life: no less than 20,000 times
VS1-40.5 Technical data
| Items | Unit | Date |
| voltage |
KV |
40.5 |
| short-time power frequency withstand voltage (1min) | 95 | |
| lightning impulse withstand voltage (peak) | 185 | |
| frequency | Hz | 50/60 |
| current | A | 1250 1600 2000 2500 4000 |
| short-circuit drop-out current | KA | 25 31.5 |
| short-time withstand current | 25 31.5 | |
| short-time continual time | s | 4 |
| peak withstand current | KA | 63 80 |
| short-circuit closing current | 63 80 | |
| single/ back-to-back capacitor bank drop-out current | A | 630/400 |
| Opening time (rated volt.) | ms | 35~60 |
| Closing time (rated volt.) | 50~100 | |
| Mechanical life | times | 20000 |
| break times for rated short drop-out current | s | 20 |
| operation voltage | V | AC110/220 DC110/220 |
| current of power storing motor | W | 230 |
| Average opening speed | m/s | 1.6~2.0 |
| Average closing speed | 0.5~0.8 | |
| operation procedure |
opening-0.3s-closing opening-180s-closing opening |
Knkong Electric 33KV switchgear has served the international market for over the past 10 years.
Similar Products
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Knkong Electric Co.,Ltd
Location
No. 25 Street , Hanghai Road, Zhengzhou,Henan,China
Contact Person
Ken Chan (English)