Industrial 80KW 100KVA UPS Three Phase 380v 400v 415v Power Supply
Industrial 80KW 100KVA UPS Three Phase 380v 400v 415v Power Supply
ZGD310/ZGD330 provides maximum protection for vital mission-critical networks, security applications (electro- medical)and industrial applications thanks to its outstanding mechanical and electrical design.
The load is powered continuously by the inverter with a filtered, stabilised and regulated sinewave supply. The input and output EMI filters considerably increase the immunity of the load to mains disturbances and surges.
The ZGD310/ZGD330 uses on-line double conversion technology (VFI) with isolation transformer on theinverter output.
The ZGD310/ZGD330 is supplied with Watch & Save 3000 software as standard and can be remotely monitored
using the Power NetGuard system from anywhere in the world. Additional battery extension packs allow the standard
Specification
|
model |
ZGD33 100K |
|||||||||||
|
capacity |
80 KW |
|||||||||||
|
INPUT |
||||||||||||
|
Nominal Voltage |
3 x 380VAC/400VAC (3Ph + N) |
|||||||||||
|
Acceptable Voltage Range |
305VAC ~ 460VAC |
|||||||||||
|
Frequency |
50/60 Hz ± 10 % |
|||||||||||
|
INVERTER |
||||||||||||
|
Nominal Voltage |
3 x 380VAC/400VAC (3Ph + N) |
|||||||||||
|
Precision |
Stationary: ±1% ; Transitory: ±5% (load variations 100-0-100%) |
|||||||||||
|
Frequency |
50/60 Hz synchronised ±1 % With mains absent ±0.1 Hz |
|||||||||||
|
Max. Synchronisation Speed |
±1 Hz/s |
|||||||||||
|
Waveform |
Pure Sinewave |
|||||||||||
|
Total Harmonic Distortion (THDv) |
< 2% (Linear Load) ; < 5% (Non-linear Load) |
|||||||||||
|
Phase Displacement |
120º ±1% (balanced load) ; 120º ±2% (imbalances 50% of the load) |
|||||||||||
|
Dynamic Recovery Time |
3 cycles at 98 % of the static value |
|||||||||||
|
Admissible Overload |
110% for 10min; 150% for 60sec ; >160% for 200ms |
|||||||||||
|
Admissible Crest Factor |
3:1 |
|||||||||||
|
Admissible Power Factor |
0.6~1 (inductive or capacitive) |
|||||||||||
|
Current Limit |
High overload, short-circuit: RMS Voltage Limit ; High Crest-Factor current: Peak Voltage Limit |
|||||||||||
|
STATIC BYPASS |
||||||||||||
|
Type |
Solid state |
|||||||||||
|
Voltage |
3 x 380VAC/400VAC (3Ph + N) |
|||||||||||
|
Frequency |
50/60 Hz |
|||||||||||
|
Activation Criterion |
Microprocessor control |
|||||||||||
|
Transfer Time |
Zero |
|||||||||||
|
Admissible Overload |
150% for 1 hour; 180% for 30sec; >200% for 200ms |
|||||||||||
|
Transfer to Bypass |
Immediate, for overloads above 160% |
|||||||||||
|
Retransfer |
Automatic after alarm clear |
|||||||||||
|
BATTERY & CHARGER |
||||||||||||
|
Battery Type and Numbers |
12VDC x 32 pcs (29~32 pcs adjustable) |
|||||||||||
|
Nominal Battery Voltage |
384 VDC (Based on 32pcs batteries) |
|||||||||||
|
Charging Method |
CC/CV |
|||||||||||
|
Charging Current |
Default: 10A. Max. 40A |
|||||||||||
|
Charging Voltage |
432 VDC (Based on 32pcs batteries) |
|||||||||||
Packing & Delivery

We are based in Guangdong, China, start from 2013,sell to Domestic Market(50.00%),Southeast Asia(5.00%). There are total about 101-200 people in our office.
2. how can we guarantee quality?
Always a pre-production sample before mass production;
Always final Inspection before shipment;
3.what can you buy from us?
Industrial UPS,Capacitive UPS,Modular UPS,High Frequency UPS,Low Frequency UPS
4. why should you buy from us not from other suppliers?
As a manufacturer with over 10 years of experience, Shenzhen ZGD Technology Co., Ltd. has more than 10 production lines which can produce 100,000 pieces of UPS every month. Over 10% of our staff members are engineers and professional technicians and more
5. what services can we provide?
Accepted Delivery Terms: FOB,CIF,EXW;
Accepted Payment Currency:USD,CNY;
Accepted Payment Type: T/T,L/C,Western Union;
Language Spoken:English,Chinese
Title goes here.
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.