Joyoung International Trading Co.,Ltd
                                                                                                           
Verified Supplier
13 Years
Since 2013
Menu

ABB DSDO 115 57160001-NF Digital Output Board

Price Negotiable
Price: inquiry
MOQ: 1 Piece
Delivery Time: 5-8 work days
Brand: ABB
Product Description

ABB DSDO 115 57160001-NF Digital Output Board

 

 

Product Details:

 

Brand Name ABB
Model DSDO 115
Product ID 57160001-NF
Catalog ABB Advant OCS
Origin Sweden (SE)
Dimension 32.4*22.5*2.2 cm
Weight 0.4kg
HS Code 8537101190
Payment T/T
Sales Price $1000
Warranty 12 months
Lead time 3-5 work days

 

 

Additional Information:

 

Board type Description Connection Unit Cable
DSDO 115 32 channels, 24 V d.c. 4 x DSTD 108 / DSTD 108L(1) These connection units provide 8 relay outputs each, 24 - 250 V a.c./ d.c. max 3 A DSTK 226L3
DSDO 115 32 channels, 24 V d.c. Variants below provides object oriented connection to DSDI 110A and DSDO 115, various rated input voltages: 24 V d.c. DSTD 145 120 V a.c. DSTD 147 230 V a.c. DSTD 148 These connection units include 8 relay outputs each, 24 - 250 V a.c./ d.c. max 3 A. DSTK 226L5 DSTK 226L5 DSTK 226L5
DSDO 115 32 channels, 24 V d.c., short-circuit protected, transistor output, max. 150 mA DSTD 110A / DSTD 190 DSTK 221L3

 


Description:

 

S100 I/O is the group of input and output boards located in the I/O subrack. The I/O subrack communicates with the controller subrack using Bus Extension to S100 I/O. Single and redundant Bus Extension to S100 I/O are available. Redundant S100 I/O Bus Extension requires redundant processor module. Electrical and optical bus extensions are provided. See the outline presentation of the bus extension in Section 1.7.7, Communication or to the separate documentation mentioned.

 

Information in this section is divided according to the different categories of boards and subdivided into Main Point, available Board Types and a signal Block Diagram.

 

Regarding connection units and internal cables used in the hazardous and HART applications you are referred to the separate documentation.

 

Digital Input,Main Points

 

• All digital inputs are opto-isolated from the system potential. Grouping of channels, with respect to isolation, can exist. See information given with the actual board type and connection unit type.

 

• You can select the mode of data base updating, either by interrupts or by scanning. The scan cycle times are normally selected from the range 10 ms to 2 s.

 

• Some boards offer pulse extension, for example to avoid rapid scanning of push buttons.

 

• The input signals are filtered on the input board to suppress the effects of electrical interference or bouncing contacts. The filter time is fixed to 5 ms or configurable depending on board type selected.

 

• Board types offering interrupt-controlled scanning are most suitable to get time-tagged events.

 

 

 

Datasheet Link: 

 

 

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.