20KVA/18KW Online High Frequency UPS For Miniaturized Data Center Storage
20KVA/18KW Online High Frequency UPS For Miniaturized Data Center Storage
Feature of High Frequency UPS
Simple
Hot-swappable power module, bypass module and control module simplify maintenance and expansion in 5 minutes
Green
Compact design, saving the footprint by 50%
96% system efficiency, high efficiency at light-load
Reliable
The redundant architecture eliminates single point of failure
ultra-wide input voltage range, suitable for the
worst power grid
| Model | EH9335 Pro-20KS | EH9335 Pro-30KS | EH9335 Pro-40KS | EH9335 Pro-60KS | EH9335 Pro-80KS | ||
| Power | 20KVA/18KW | 30KVA/27KW | 40KVA/32KW | 60KVA/54KW | 80KVA/64KW | ||
| Input | Input | Three Phase Four Line+Ground (3PH 4W+G) | |||||
| Rated Power | 380/400/415VAC | ||||||
| Voltage Range | 208~478VAC | ||||||
| Frequency Range | 45~55HZ At 50HZ / 54~66HZ At 60HZ (Auto Sensing) | ||||||
| Power Factor | ≥0.99 | ||||||
| Input Current Harmonic | ≤ 3%(100%Nonlinear load ) | ||||||
| Bypass Range | Bypass protection voltage upper limit 220V + 25%(Optional+ 10% + 15% + 20%) 230V + 20%(Optional+ 10% +15%) 240V + 15% (Optional+10%) |
||||||
| Bypass protection voltage lower limit -45%(Optional -20% -30%) | |||||||
| Bypass Frequency Protection Range±10% | |||||||
| Output | Output | Three Phase Four-line+Ground Or Single Phase+N | |||||
| Rated Voltage | 380/400/415VAC Or 220/230/240VAC | ||||||
| Power Factor | 0.9 | ||||||
| Voltage Accuracy | ±1% | ||||||
| Output Frequency | Utility Mode | Synchronous with input when the mains frequency exceeds ±10% maximum (±1% ±2% ±4% ±5% can be set) the output frequency is 50*(±0.2)HZ |
|||||
| Battery Mode | (50/60±0.2%)HZ | ||||||
| Load Peak Ratio | 3:1 | ||||||
| Output Voltage Distortion | ≤ 2% Linear Load ≤ 5% Nonlinear Load |
||||||
| Battery | Efficiency | Normal Mode≥ 94.5% | |||||
| Battery Voltage | Optional :±192V±216V±240V DC (±16/18/20 PCS) | ||||||
| Charging Current | 10A max | ||||||
| Transfer time | Utility mode to bypass mode: 0ms (tracking) utility mode to battery mode: 0ms |
||||||
| Protection | Overload Capbility | Normal Mode | Load ≤ 110%, 60mins; ≤ 125%, maintain 10mins; ≤150% for 1min ≥ 150% shut down immediately. |
||||
| Over Temperature Protection | Normal Mode:Switch to bypass mode; battery mode. Turn off the output immediately |
||||||
| Emergency Shutdown (EPO) |
Turn off the output immediately. | ||||||
| Operating Environment | Communication Connection | USB, RS485, dry contact, parallel (optional), SNMP card (optional), relay card (optional) | |||||
| Working Temperature | 0℃~40℃ | ||||||
| Storage Temperature | -25℃~55℃ | ||||||
| Relative Humidity | 0~95% No Condensation | ||||||
| Altitude | < 1500m, when above 1500m, derate according to GB/T 3859.2 | ||||||
| Physical characteristics | Size (D*W*H) | 680*250*540mm | 700*250*960mm | ||||
| Net Weight(kg) | 45 | 46 | 48 | 80.5 | 82.5 | ||
| Executive Standard | YD/T1095-2008 | ||||||
High Frequency UPS Application Field
High Frequency UPS is Applied to small and medium-sized enterprises, large enterprise branches, banking outlets ,miniaturized data center storage, network equipment, VOIP, communications equipment, automation equipment, office equipment terminal precision equipment, etc.
- Rated Power 20KVA 30KVA 40KVA 60KVA 80KVA
- TRANSIENT VOLTAGE SURGE SUPPRESS Protect Function For FAX,TELEPHONE,MODEM;
- Machine Efficiency Greater Than 97%, Input Power Factor Greater Than 0.99, Input Current Harmonics Less Than 5%;
- Optional SNMP For Monitoring.

Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.