Comprehensive Electrical Power Quality Analyzer Rechargeable With 4 Channel Current

Price Negotiable
Price: negotiation
MOQ: 1 set
Delivery Time: 5-10 working days
Brand: HAOMAI
Product Description

Power Quality Analyzer

 

Model: PQA-500

Power Quality Analyzer PQA-500 is a comprehensive test instrument developed by HAOMAI ELECTRIC and specially designed for field test of three phases, multi-functional and intelligent, concise man-machine operation. It is easy to use, large LCD screen display, high resolution, interface in both Chinese and English, shock-proof shell structure and so on. It can simultaneously measure the 4-channel current (ABC three phase and neutral wire cur-rent), 4-channel voltage (ABC three-phase voltage and neutral line voltage to ground), the peak value of current voltage, maximum/minimum value over a period, three-phase imbalance factor, short-time voltage flicker, transformer K factor, active power, reactive power, apparent power, power factor and displacement power factor, active power, reactive power, apparent power, total harmonic distortion and harmonic etc.; display real-time waveform, harmonic ratio bar charts of current voltage; dynamically capture instantaneous change of voltage current, monitoring starting current, monitoring the power parameters and generate the alarm list, generate the trend chart for a long time record test data.

 

Technical Data

Power supply Rechargeable lithium-ion battery packs 9.6V, backup charger.
Battery indicator Battery symbol shows dump energy. When the voltage is too low, automatic shutdown after the 1 minute.
Power consumption Current consumption of normal test 490 mA, continuous working for 8 hours.
Display mode LCD color screen, 640dots×480dots, 5.6 inches, display domain: 116mm×88mm.
Size of clamp

HM-008B small sharp current clamp: 7.5mm×13mm;

HM-040B circle current clamp: 35mm×40mm;

HM-068B circle current clamp: 68mm×68mm.

HM-300F Flexible Coil Current Sensor (with Integrator) : Ф300mm

Instrument dimensions L×W×H: 240mm×170mm×68 mm.
Number of channels 4U/4I.
Phase-to phase voltage 1.0V~2000V.
Phase-to-neutral voltage 1.0V~1000V.
Current

HM-008B current clamp: 10mA~10.0A;

HM-040B current clamp: 0.10A~100A;

HM-068B current clamp: 1.0A~1000A;

HM-300F Flexible Coil Current Sensor (with Integrator) : 10A ~ 3000A

Frequency 40Hz~70Hz.
Parameters of electricity W, VA, Var, PF, DPF, cosφ, tanφ.
Energy parameters Wh, Varh, Vah.
Harmonic Order 0~50.
Total harmonic distortion Order 0~50, each phase.
Expert mode Yes
Number of Transient records 150 sets
Voltage flicker Yes
Starting current mode Yes, 100 seconds.
3 phases unbalance Yes
Record 300 days(simultaneous recording 20 parameters, record one point every 5 seconds).
Min/Max recorded value Measurement of maximum and minimum values over a period of time.
Alarm 40 different types of parameter selections, 12,800 sets alarm logs.
Peak Yes
Phasor diagram display Automatically.
Capacity of snapshots 60
Menu language English/Chinese.
Communication USB.
Automatic switching off When an alarm campaign is initiated or a search for transients, an inrush current capture, or a trend recording is pending or in progress, the device is not automatic switching off.
In other test mode, 15 minutes without keystrokes, automatic shutdown after prompt 1 minute.
Backlight function Yes, suitable for use at night and dark place.
Weight Host: 1.6kg (with battery).
HM-008B small sharp current clamp: 170g×4;
HM-040B circle current clamp: 190g×4;
HM-068B circle current clamp: 510g×4;
HM-300F Flexible Coil Current Sensor (with Integrator) : 330g×4;
Test wires and power adapter: 900g;
Total weight: about 9.2kg (with packaging).
Length of voltage test wire 3m
Length of current sensor wire 2m
Working temperature and humidity -10°C~40°C; below 80%Rh.
Storage temperature and humidity -10°C~60°C; below 70%Rh.
Input impedance Input impedance of test voltage: 1MΩ.
Withstand voltage Withstand 3700V/50Hz sinusoidal AC voltage for 1 minute between instrument wiring and shell.
Insulation Between instrument wiring and shell ≥10MΩ.
Structure Double insulation, with insulation vibration-proof sheath.
Safely rules IEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326, Pollution degree: 2.

 

Measuring Accuracy of PQA-500(current clamp excluded)

Measurement Range Display resolution The maximum error in the range of the reference
Frequency 40Hz~70Hz 0.01Hz ±(0.03)Hz
True RMS phase-to-neutral voltage 1.0V~ 1000V Min resolution 0.1V ±(0.5%+5dgt)
True RMS phase-to phase voltage 1.0V~ 2000V Min resolution 0.1V ±(0.5%+5dgt)
DC voltage 1.0V~ 1000V Min resolution 0.1V ±(1.0%+5dgt)
True RMS current 10mA~ 1000A Min resolution 1mA ±(0.5%+5dgt)
Peak of phase-to-neutral voltage 1.0V~ 1414V Min resolution 0.1V ±(1.0%+5dgt)
Peak of phase-to-phase voltage 1.0V~ 2828V Min resolution 0.1V ±(1.0%+5dgt)
Current peak 10mA~ 1414A Min resolution 1mA ±(1.0%+5dgt)
Peak factor 1.00~ 3.99 0.01 ±(1%+2dgt)
4.00~ 9.99 0.01 ±(5%+2dgt)
Active power 0.000W~ 9999.9kW Min resolution 0.001W

±(1%+3dgt)

Cosφ≥0.8

±(1.5%+10dgt)

0.2≤Cosφ<0.8

Reactive power, inductive or capacitive

0.000VAR~

9999.9kVAR

Min resolution 0.001VAR

±(1%+3dgt)

Sinφ≥0.5

±(1.5%+10dgt)

0.2≤Sinφ<0.5

Apparent power

0.000VA~

9999.9kVA

Min resolution 0.001VA ±(1%+3dgt)
Power factor -1.000~ 1.000 0.001

±(1.5%+3dgt)

Cosφ≥0.5

±(1.5%+10dgt)

0.2≤Cosφ<0.5

Active energy 0.000Wh~ 9999.9MWh Min resolution 0.001Wh

±(1%+3dgt)

Cosφ≥0.8

±(1.5%+10dgt)

0.2≤Cosφ<0.8

Reactive energy, inductive or capacitive

0.000VARh~

9999.9MVARh

Min resolution 0.001VARh

±(1%+3dgt)

Sinφ≥0.5

±(1.5%+10dgt)

0.2≤Sinφ<0.5

Apparent energy

0.000VAh~

9999.9MVAh

Min resolution 0.001VAh ±(1%+3dgt)
Phase angle -179°~ 180° ±(2°)

Tanφ

(VA≥50VA)

-32.76~ 32.76 Min resolution 0.001 φ:±(1°)

Phase shift of power factor

(DPF)

-1.000~ 1.000 0.001 φ:±(1°)

Harmonic ratio

(order 1 to 50) (Vrms>50V)

0.0%~ 99.9% 0.1% ±(1%+5dgt)

Harmonic angle

(Vrms>50V)

-179°~ 180° ±(3°) harmonics of order 1 to 25
±(10°) harmonics of order 26 to 50

Total harmonic ratio

(THD or THD-F)≤50

0.0%~ 99.9% 0.1% ±(1%+5dgt)

Distortion factor

(DF or THD-R)≤50

0.0%~ 99.9% 0.1% ±(1%+10dgt)
Transformer K factor 1.00~ 99.99 0.01 ±(5%)
3 phases unbalance 0.0%~ 100% 0.1% ±(1%)

 

Current Clamp(optional)

Type True RMS current Max error of true RMS current Max error of phase angle
HM-008B current clamp 10mA~ 99mA ±(1%+3dgt) ±(1.5°),Arms≥20mA
100mA~ 10.0A ±(1%+3dgt) ±(1°)
HM-040B current clamp 0.10A~ 0.99A ±(1%+3dgt) ±(1.5°)
1.00A~ 100A ±(1%+3dgt) ±(1°)
HM-068B current clamp 1.0A~ 9.9A ±(2%+3dgt) ±(3°)
10.0A~ 1000A ±(2%+3dgt) ±(2°)
HM-300F Flexible Coil Current Sensor (with Integrator) 10A~99A ±(1% + 3dgt) ±(3°)
100AA~3000A ±(1% + 3dgt) ±(2°)

 

Power Quality Analyzer PQA-500 is powerful tool for testing engineers.

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company HAOMAI ELECTRIC TEST EQUIPMENT CO.,LTD
Location 806, No.24 Nanlian Road, Nanlian Community, Longgang Street, Longgang District, Shenzhen City, 518116 China
Contact Person William Wang

Request A Quote

Please check your email address.