0393.0200 0393 0200 Nitrogen Dioxide Gas Sensor For Measuring Concentration Of Nitrogen Dioxide In Flue Gas
Features:
- Easy to Replace: The pre - calibrated sensor can be simply plugged into the appropriate flue gas analyzer, allowing users to replace the sensor on - site by themselves.
Application:
- Flue Gas Measurement: It is mainly used for measuring the concentration of nitrogen dioxide in flue gas, and is suitable for being used with Testo 350 exhaust gas analysis systems and other similar equipment.
| Target Gas | Nitrogen Dioxide (NO₂) |
| Measurement Range | 0 - 500 ppm |
| Resolution | 0.1 ppm |
| Weight | 18 g |
| Dimensions | 40 x 30 x 30 mm (LxWxH) |
| Product/Housing Material | Plastic |
| Product Colour | Grey; Black |
| Output Signal | 370±70nA/ppm (Based on similar models, for reference only) |
| Temperature Range | - 40°C to 45°C (Estimated, for reference) |
| Pressure Range | Standard atmospheric pressure±10% (Estimated, for reference) |
| T90 Response Time | < 40sec (Estimated, for reference) |
| Relative Humidity Range | 15% to 90% RH |
| Zero - point Output (Pure Air, 20°C) | 0 to 0.2ppm (Estimated, for reference) |
| Zero - point Drift (+20°C to 40°C) | - 1ppm (Estimated, for reference) |
| Long - term Output Drift | < 2% signal loss/month (Estimated, for reference) |
| Recommended Load Resistance | 10 - 33Ω (Estimated, for reference) |
| Bias Voltage | Not Required |