2V 300ah Gel AGM SLA Vrla Deep Cycle Maintenance Free Sealed Lead Acid Battery
Amaxpower 2V Sealed VRLA AGM Deep cycle gel battery for solar (2V 300Ah)
Amaxpower CG Series 2V 300ah AGM Sealed Lead Acid Battery Gel Battery for Solar and UPS Emergency Systems
AMaxpower CG Series 2V Long Life Deep Cycle AGM batteries are recognized as the most reliable and high quality battery system in the industry. They are designed with advanced patented AGM technology, Long service life designed with 15 years, the batteries comply to the most popular international standards, such as IEC60896-21/22, BS6290-4, Eurobat Guide.
1. CG series 2V deep cycle AGM battery adopts unique grid structure, special super corrosion-resistant alloy and unique active material formula, which can improve the efficiency, so CG series battery recover performance is excellent after deep discharge even discharge to empty, also with the advantage of high durability, enough capacity and long cycle life.
2.With a gas recombination efficiency of 99%, such batteries are completely maintenance free operation, non-spillable, no gassing, no need for replenishment. Items can be used at vertical or horizontal orientation.
Specification
| Rate Voltage | 2V(Single cell) | |
| Nominal Capacity | 300Ah @10 hour-rate | |
| Dimension | Length | 171±2mm (6.70 inches) |
| Width | 151±2mm (5.94 inches) | |
| Container Height | 330±2mm (13.0 inches) | |
| Total Height | 365±2mm (14.37 inches) | |
| Weight | Approx. 17.5kg (38.58lbs) | |
| Container Material | ABS | |
| Reference Capacity (25°C) | 20hr (15.8A) | 315Ah |
| 10hr (30A) | 300Ah | |
| 5hr (54A) | 270Ah | |
| 3hr (80A) | 240Ah | |
| 1hr (195A) | 195Ah | |
| Max. Discharge Current | 1800A (5S) | |
| Internal Resistance (25°C) | Approx. 0.7mΩ | |
| Cycle Use Voltage |
Initial Charging Current: Less than 75A Voltage: 2.33-2.37V @ 25°C (77°F) |
|
| Float Charging Voltage | 2.24-2.28V @ 25°C (77°F) | |
| Operating Temperature Range | Discharge | -20~60°C |
| Charge | -10~60°C | |
| Storage | -20~60°C | |
| Nominal Operating Temperature Range | 25°C±3°C (77±5°F) | |
| Capacity affected by Temperature (20 hour rate) | 40°C (104°F) | 102% |
| 25°C (77°F) | 100% | |
| 0°C (32°F) | 85% | |
| -15°C (5°F) | 65% | |
| Self-Discharge | Less than 3% at 25°C (77°F) per month | |
Applications
Industry use, Communication equipment, Telecommunication control equipment; Emergency systems; Electric power systems; Golf carts; Caravan; Power station; Nuclear power station; Solar power and wind power systems; Load leveling and storage equipment; Marine equipment; Power generation plants; Alarm systems, UPS and inverters; Medical equipment; Fire and security systems, Control equipment; Stand-by electric power.