12V 180Ah Front Terminal Gel Solar Battery For UPS / EPS / Telecom
Maintenance Free Front Terminal Gel Solar Battery for UPS/EPS /Telecom (12V 180Ah)
The Amaxpower Maintenance Free Lead Acid 12V 180Ah battery is a type of deep-cycle battery commonly used in applications such as solar power systems, electric vehicles, backup power systems, and marine applications. Here are some key features and considerations regarding this battery:
1:Battery Type: The Amaxpower battery is a sealed lead acid (SLA) battery, also known as a valve-regulated lead-acid (VRLA) battery. It is designed to be maintenance-free, meaning it does not require regular water refilling or electrolyte checks.
2:Voltage and Capacity: This battery has a nominal voltage of 12 volts, which is a common voltage for many applications. The capacity of 180Ah (ampere-hours) indicates the amount of energy the battery can store. Higher Ah ratings generally mean the battery can provide power for a longer duration.
3:Deep-Cycle Design: This battery is specifically designed for deep-cycle applications, which means it can discharge a significant portion of its capacity before needing to be recharged. It is well-suited for applications that require sustained power over extended periods, such as powering appliances or running equipment.
4:Maintenance-Free: As a sealed lead acid battery, the Amaxpower battery is designed to be maintenance-free. It is sealed to prevent acid leakage and does not require regular electrolyte checks or water refilling. This makes it more convenient and user-friendly compared to traditional flooded lead-acid batteries.
5:Mounting and Installation: The Amaxpower battery can be mounted in various orientations, including vertical and horizontal positions. It is important to follow the manufacturer's guidelines for proper installation and ensure that the battery is securely mounted to prevent any damage or accidents.
6:Charging and Discharging: When charging the battery, it is essential to use an appropriate charger that is compatible with sealed lead-acid batteries. Overcharging or undercharging the battery can affect its performance and lifespan. It is also important to avoid deep discharges below the recommended minimum voltage, as this can cause damage to the battery.
7:Lifespan and Durability: The lifespan of the Amaxpower battery can vary depending on factors such as usage, charging practices, and operating conditions. With proper care and maintenance, a well-designed deep-cycle battery like this can last for several years. It is important to refer to the manufacturer's guidelines for specific information on lifespan and warranty.
8:Safety Considerations: Like all batteries, it is important to handle the Amaxpower battery with caution and follow appropriate safety procedures. Avoid short-circuiting the battery terminals, exposing it to extreme temperatures, or puncturing the battery casing.
It's worth noting that the information provided is based on a typical understanding of maintenance-free lead-acid batteries, and specific details may vary depending on the manufacturer and model. For accurate and detailed information about the Amaxpower Maintenance Free Lead Acid 12V 180Ah battery, it's recommended to refer to the manufacturer's documentation or contact their customer support.
Specification
| Nominal Voltage | 12V (6 cells) | |
| Nominal Capacity | 180Ah@10 hour-rate | |
| Dimension | Length | 546±1(21.5 inches) |
| Width | 124±1(4.88 inches) | |
| Height | 325±2(12.79 inches) | |
| Total Height | 325±2(12.79 inches) | |
| Weight | Approx. 53kg (116.8lbs) | |
| Reference Capacity (25°C/77°F ) | 20 hour rate (9.35A) | 187Ah |
| 10 hour rate (18.0A) | 155Ah | |
| 5 hour rate (32.4A) | 162Ah | |
| 3 hour rate (48.0A) | 144Ah | |
| 1 hour rate (117A) | 117Ah | |
| Max. Discharge Current (25°C/77°F) | 1080A (5S) | |
| Internal Resistance | Full charged at 25℃(77°F): Approx. 5.0mΩ | |
| Charge (Constant Voltage) (25°C/77°F) | Cycle Use |
Voltage: 14.4-15.0V Initial Charging Current: Less than 45A |
| Float Use | Voltage: 13.6-13.8V | |
| Operating Temperature Range | Discharge | -20~60°C |
| Charge | 0~60°C | |
| Storage | -20~60°C | |
| Nominal Operating Temperature Range | 25°C ±3°C(77±3°F) | |
|
Capacity affected by Temperature (20 hour rate) |
40°C(104°F) | 102% |
| 25°C(77°F) | 100% | |
| 0°C(32°F) | 85% | |
| -15°C(5°F) | 65% | |
| Self-Discharge (25°C/77°F) | After 3 month | 91% |
| After 6 month | 82% | |
| After 12 month | 64% | |
| Container Material | ABS Plastic | |
Applications
1. Suitable for 19inch and 23inch power cabinet.
2. Used in telecom system including exchange board, microwave station, mobile base station, data center, radio and broadcast station.
3. Great for power supply system of private network or LAN.
4. Used as signal system battery and emergency lighting system battery.
5. Perfect for EPS and UPS system.
6. Solar and wind system