Electrical Automatic IG 100 Fire Suppression System Inergen Fire Extinguisher 1910mm
High-Quality Inert Gas Nitrogen IG100 Fire Extinguishing System Without Pollution
Inert gas fire extinguishing systems are the safe, natural way to extinguish a fire. Because of its unique patented valve assembly, the agent enters the protected zone within the industry required 60 seconds but at a steady flow rate — preventing destructive turbulence from occurring. This constant flow rate allows for the use of small-diameter, low pressure (and less expensive) piping from the inert gas container all the way to the nozzle. And, the necessary venting area is much smaller, which can reduce installation costs by as much as 60% on venting hardware.
Parameters
| No. | Specification | Technical Parameter | |
| 1 | Working Pressure | 20MPa | 30MPa |
| 2 | Device Model | QMD20/80 | QMD30/80 |
| 3 | Capacity | 80Ltr | 80Ltr |
| 4 | Filling Capacity of Gas | 20kg | 24.68kg |
| 5 | Outside Diameter of Cylinder | Φ267mm | Φ267mm |
| 6 | Height of Cylinder | 1910mm | 1770mm |
| 7 | Spraying Time | ≤120s | ≤120s |
| 8 | Max Filling Rate | 0.25kg/L | 0.309kg/L |
| 9 | Power | DC24V/1.6A | DC24V/1.6A |
| 10 | Nitrogen Pressure of Driving Device | 6.0±1.0MPa(20℃) | 6.0±1.0MPa(20℃) |
| 11 | Condition of Reserving Room for Container | temperature: 0~50℃ | temperature: 0~50℃ |
| 12 | Max Working Pressure | 23.2MPa | 36.6MPa |
| 13 | Min Working Pressure | 18MPa | 27MPa |
Components
Storage cylinder group, storage cylinder group frame, nitrogen driving device, nitrogen driving device frame, the cylinder valve, liquid flow check valve, air flow check valve, electromagnetic starter, gas conveying pipeline, collecting pipe, choice valve, three links, reducer tee, reduceing elbow, flange, safety valve, pressure transmitter, pipe, nozzle, chemicals, fire detector, fire controller, sound and light alarm, alarm bell, gas light, emergency start / stop button, etc.
Application
• Computer room, communication room, power distribution room, library, archives,
Museum, etc.
• Be used for electrical fire, liquid fire, solid fire, gas fire which can be cut off the gas
source before extinguishing occur, etc.
Advantages
- After spraying, the system does not need to replace any parts, simple dis-assembly and secondary filling, the system can be quickly put into operation.
- The opening area of the pressure-relief device is reduced. the input cost of the pressure-relief device is directly reduced, and the safety buckle is installed and arranged more simply.
- Nitrogen fire extinguishing system(IG-100) can be widely used to make rapid response to fire, protect staffs on sites, sudden fire, important places sensitive to chemical reaction and effectively protect the safety of personnel and property.
Packages
We always pack it with polyfoam first and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.