VLF Series High Voltage Testing 0.01Hz 80kv Very Low Frequency AC Hipot Tester
Price:
USD1.0 Cable Withstand Voltage Tester / set
MOQ:
1 set Cable Withstand Voltage Tester
Delivery Time:
In 10 days after the order is confirmed
Brand:
Delta
Product Description
VLF Series High Voltage Testing 0.01Hz 80kv Very Low Frequency AC Hipot Tester
Introduction:
- VLF Series High Voltage Testing 0.01Hz 80kv Very Low Frequency AC Hipot Tester is designed and manufactured for electrical equipment very low frequency withstand voltage test.
- A very low frequency withstand voltage test is essentially an alternative to the power frequency withstand voltage test. It is much smaller, lighter, and more portable than a power frequency and withstands voltage tester.
- It is proved at home and abroad that 0.1Hz ultra-low frequency withstands voltage test can replace the power frequency withstand voltage test.
- It can be applied for 10kV, 35kV, and 300MW thermal power machines, 10kV, 35kV power transformers, and other electrical equipment.
Parameters:
- Max voltage output: refer to Table 1;
- Output frequency: 0.1Hz, 0.05Hz, 0.02Hz;
- Measurement accuracy: 2.5%;
- Positive and negative voltage peak errors < 2.5%RDG+0.3%FS;
- Voltage waveform distortion: <3%;
- Insulation resistance measurement error: <2.5%;
- Leakage current measurement error: <2.5%;
- Power supply:AC220V ± 10%, 50Hz/60Hz;
- Environment temperature: 0~50°C; Humidity:≤85%RH;
| Model | Rated Voltage/Current | Load Carrying Capacity | Power fuse wire | Weight |
| VLF-30 | 30kV/20mA (Peak) |
0.1Hz, 0.5µF~1.1µF | 10A | Controller:6kg Booster: 35kg |
| 0.05Hz, 0.5µF~2.2µF | ||||
| 0.02Hz, 0.5µF~5.5µF | ||||
| VLF-40 | 40kV/30mA | 0.1Hz ≤ 1.1uF | 20A | Controller: 6kg Booster: 50kg |
| 0.05Hz ≤ 2.2uF | ||||
| 0.02Hz ≤ 5.5uF | ||||
| VLF-50 | 50kV/30mA (Peak) |
0.1Hz, 0.5µF~1.1µF | 20A | Controller:6kg Booster: 50kg |
| 0.05Hz, 0.5µF~2.2µF | ||||
| 0.02Hz, 0.5µF~5.5µF | ||||
| VLF-60 | 60kV/30mA (Peak) |
0.1Hz, ≤0.5µF | 9A | Controller:4kg Booster 1(30kV):25kg Booster 2(30kV):25kg |
| 0.05Hz, 0.5µF~1µF | ||||
| 0.02Hz, 0.5µF~2.5µF | ||||
| VLF-80 | 80kV/30mA (Peak) |
0.1Hz, ≤0.5µF | 12A |
Controller:4kg |
Features:
- VLF AC Hipot Tester with over voltage and over current protection;
- Data of current, voltage, and wave form can be directly sampled at high voltage side, so the data is real and accurate;
- With color man-machine interface touch control plus controls modular software operating system, precise and intuitive;
- Multi-purpose, can simultaneously measure tested object's capacitance, insulation resistance, leakage current, and AC withstand voltage test;