750kVA Cummins Diesel Generators Powered By CCEC KTA38-G2 For Industrial Field
750kVA Cummins diesel generators powered by CCEC KTA38-G2 for Industrial field
General Configuration for 750kVA Cummins Diesel Generators:
- Brand new CUMMINS water-cooled diesel engine.
- Brand new Leroy Somer AC alternator with customizable ratings.
- Radiator with engine-driven fan mounted on skid.
- Cummins diesel generators equipped with Denmark DEIF SGC-420 auto start control panel.
- CHNT brand Circuit Breaker installed in Cummins diesel generators.
- Anti-vibration mountings for reduced vibrations.
- 12/24V DC electric start system with VARTA brand lead-acid type starting batteries.
- Industrial silencers with flexible connectors and elbow.
- Base fuel tank integrated into the diesel generator for 4 hours of running time, with a fuel gauge in the base frame.
- Test report, set of drawings, and O&M manuals provided for Cummins diesel generators.
- Standard toolkit included.
750kVA Cummins Diesel Generators Data:
| 750kVA Cummins Diesel Generators Specifications | |||||
| Model | Engine | Alternator | Controller | Output | |
| TG825CS | KTA38-G2 | TAL-A49-B | DEIF SGC-420 | 750kVA | |
|
Remark: (1) Payment Terms: FOB Fuzhou Port (2) Delivery: 15 working days (3) Payment method: 30% deposit, 70% before delivery (4) Price Valid time: 30 Days (5) Option: Integrated Fuel Tank, Water Heater, ATS, PMG Generator, SYNC Function, 12/24 Hours Fuel Tank, 3000 hours Spare Parts
|
|||||
| General Date of 750kVA Cummins Diesel Generators | |||||
| Engine Model | KTA38-G2 CCEC Cummins | ||||
| Alternator Mode | TAL-A49-B Leroy Somer | ||||
| Rated Output | 750kVA / 600kW | ||||
| Standby Output | 825kVA / 660kW | ||||
| Rated Speed | 1500 RPM | ||||
| Frequency | 50 HZ | ||||
| Rated Voltage | 240 / 415V | ||||
| Rated Current | 1043.4A | ||||
| Breaker | 1200 CHINT Breaker | ||||
| ATS | 1200A ATS Cabinet for option | ||||
| Power Factor | 0.8 | ||||
| Genset Phase | 3 phase, 4 – wire connection | ||||
| Fuel Tank | 8 running hours | ||||
| Noise level dB(A) @7m | 75dB(A) | ||||
| Net Weight | 7300KGS | ||||
| Genset size | L5300 * W2200 * H2300mm | ||||
| Voltage regulation rate | ≤±1% | ||||
| Random voltage variation | ≤±1% | ||||
| Frequency regulation rate | ≤±5% | ||||
| Random frequency variation | ≤±0.5% | ||||
| General specification of Engine for 750kVA Cummins Diesel Generators | |||||
| Manufacture | CCEC Cummins | ||||
| Model | KTA38-G2 | ||||
| Rated Output/Speed | 820KW/1500RPM | ||||
| Standby Output/Speed | 902KW/1500RPM | ||||
| Aspiration | Turbocharged & Intercooled | ||||
| Speed Governor | Electric | ||||
| Engine Type | 12 cylinders V Type | ||||
| Bore X Stroke | 159*159mm | ||||
| Displacement | 37.8 L | ||||
| Compression ratio | 14.5:1 | ||||
| Cooling system | Forced Water Cooling Cycle | ||||
| Rated speed | 1500rpm | ||||
| Fuel Consumption/rated output | 157.1 L / h | ||||
| Fuel Consumption/standby output | 172.9 L / h | ||||
| Starter motor | D.C. 24V Electric starting | ||||
| Alternator (Dynamo) | AC24V | ||||
| General data of Alternator for 750kVA Cummins Diesel Generators | |||||
| Alternator Model | TAL-A49-B | ||||
| Manufacture | Leroy Somer | ||||
| Rate Output | 600kW | ||||
| Rated voltage(V) | 240 / 415V | ||||
| Voltage regulation | AVR ± 1.0 % | ||||
| Working Altitude | ≤1000 | ||||
| Control System | Brushless Self Excited | ||||
| Bearing | Single Bearing | ||||
| Insulation System | Class H | ||||
| Protection | IP23 | ||||
| Power factor | 0.8 | ||||
| Winding connection | 3 phase, 4 – wire connection | ||||
| Standard configuration of 750kVA Cummins Diesel Generators | |||||
| Aluminum water tank | 50℃ | ||||
| Controller Panel | DEIF SGC-420 | ||||
| Battery | Varta Maintenance free Battery | ||||
| Silencer | Included | ||||
| Dry type air filter, fuel filter, oil filter | |||||
| 24V D.C automatic battery charger | |||||
| Max. 50 degree celsius radiator | |||||
| Batteries, rack and cable | |||||
| Ripple flex exhaust pipe, flange and muffler | |||||
750kVA Cummins Diesel Generators Silent Canopy Performance:
- Weatherproof Steel Canopy: Durable and weather-resistant construction.
- Integrated Fuel Tank: Built-in fuel tank for convenience.
- Integrated Control Panel: Easy access and operation.
- Built-in Start Battery: Reliable engine startup.
- Power Output Rapid Insert: Quick connection for power output.
- Inspection and Maintenance Doors: Convenient access for maintenance.
- Air Louvers for Intake & Exhaust: Proper ventilation.
- Exhaust Gas Silencer: Minimizes noise emissions.
- Assembled Smoke Pipes: Easy installation for smoke exhaust.
- High-Quality Silencer Cotton: Effective noise reduction.
- Strong Design Aesthetics: Visually appealing and robust.
- User-Friendly Operation: Easy to use.
OPTIONAL SUPPLY for 750kVA Cummins Diesel Generators
1) Weatherproof canopy / Soundproof canopy / Trailer-mounted
2) Engine / Alternator Pre-heaters
3) Auto load sharing & synchronization panel
4) ATS Cabinet
5) Large 12/24 hours fuel tank
6) Power output sockets
7) Cables