| FLATPACK2 110-125V RECTIFIERS Model | ||
| Part number | 241115.805 | 241119.805 |
| INPUT DATA | ||
| Voltage range (nominal) | 185 - 275 VAC/DC | 176 - 277 VAC 1) |
| Voltage range | 85 - 300 VAC/DC | 85 - 305 VAC1) |
| Frequency | 0 - 66 Hz | 45 - 66 Hz |
| Maximum current | 11.9 ARMS | 18.64 ARMS |
| Power Factor | 0.99 (@ 50-100 % load) | 0.99 (@ 50-100 % load) |
| THD (@ 230 VAC) | < 5 % (@ full load) | < 4 % (@ full load) |
| Protection | Varistor for transient protection, fuse in both lines, shutdown above 300/305 V | |
| OUTPUT DATA | ||
| Default voltage | 122.5 VDC | |
| Voltage range | 89.22) - 171.6 VDC | 90.02) - 151.25 VDC1) |
| # Pb cell supported (1.8 - 2.4 VDC/cell) | 54 - 71 | 54 -60 |
| # NiCad cell supported (1.05 - 1.65 VDC/cell) | 85 - 104 | 86 - 91 |
| Max power, nominal input | 2000 W | 3025 W1) |
| Max power, 85V input | 850 W | 1280 W |
| Max current | 16.7 A | 20 A |
| Hold-up time, default voltage and 1500 W load | 20 ms, VOUT > 99.7 VDC | 10 ms, VOUT > 99.7 VDC |
| Current sharing | ±5% of maximum current from 10 to 100% load | |
| Static voltage regulation | ±0.5% from 10% to 100% load and nominal input | |
| Dynamic voltage regulation | ±5.0% for 10-80% or 80-10% load variation, regulation time < 50ms | |
| Rippel and noise, 30 MHz bandwidth | < 500 mVPP | |
| Protection | Overvoltage shutdown, short circuit proof, high temperature, hot plug-in inrush current limiting, ORing diode |
|
| OTHER SPECIFICATIONS | ||
| Efficiency | > 94% | > 94% |
| Isolation | 3.0 kVAC – input and output, 1.5 kVAC – input earth, 1.5 kVDC – output earth 3 kVAC CAN – input, 3kVAC CAN – output |
|
| Alarms (Red LED) | Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure |
|
| Warnings (Yellow LED) | Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage |
|
| Normal (Green LED) | Input and output ok | |
| MTBF (Telcordia SR-332 Issue I method III (a)) | >391 000h (@TAMBIENT= 25°C) | >400 000h (@TAMBIENT= 25°C) |
| Operating temperature (5 - 95% RH non-cond.) Output power de-rates above temp / to |
-40 to +75°C [-40 to +167°F] +55°C / 1350W @ +75°C |
-40 to +75°C [-40 to +167°F] +50°C / 1150 W @ +75°C |
| Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing | |
| Dimensions[WxHxD] / Weight | 109 x 41.5 x 327mm (WxHxD) [4.25 x 1.69 x 13”] / 1.950 kg [4.3lbs] | |
| DESIGN STANDARDS | ||
| Electrical safety | UL 60950-1, EN 60950-1, CSA 22.2 | |
| EMC | ETSI EN 300 386 V.1.3.2 EN 61000-6-1 / -2 / -3 / -4 / -5 |
|
| Mains Harmonics | EN 61000-3-2 | |
| Environment | ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2) ETSI EN 300 132-2 2011/65/EU (RoHS) & 2008/98/EC (WEEE) |
|
| Marine compliance (EMC class B with AC filter) |
DnV Rules for Classification of Ships, High Speed & Light Craft and DnV Offshore Standards |
|
Similar Products
Related Videos
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Beijing Guoguang Xingda Technology Co.,ltd
Location
Room 701, Super Hive Technology Plaza, Cui Feng Road,Fangshan District, Beijing,China.
Contact Person
Mike Jay