3.3KV 6KV 10KV 450KW 1000KW Anchorwill / Pressure Solid-State Soft Start Device for Motor Control Power Supply AC/DC220V
| Attribute | Value |
|---|---|
| Product name | Integrated high voltage soft start cabinet |
| Starting voltage | 20%-100%Ue |
| Current limit | 150%-600% |
| Starting time | 1-150S |
| Soft stop time | 1-150S |
| Pulse start | Pulse voltage 0-100%Ue, pulse time 0-10.00S |
| Control power supply | AC/DC220V |
| Environmental conditions | -10℃~40℃; less than 95%RH; altitude below 1000m |
The MT830 high-voltage solid-state integrated soft starter builds upon the MT830 soft starter by adding a trolley-type vacuum circuit breaker and integrating high-voltage switchgear functions for enhanced performance and stability.
This model is specifically designed for starting and stopping AC motors as running power, featuring low starting current, smooth acceleration, and extended service life for both motors and starting equipment.
Soft starting optimizes water pump operation by gradually increasing current, voltage, and torque parameters during startup. This approach:
- Reduces mechanical impact and wear
- Minimizes noise and vibration
- Extends pump service life
- Lowers power demand during startup
- Protects power supply equipment from high current effects
Particularly valuable in applications requiring frequent starts (water supply systems, HVAC) or operating under poor power conditions.
The standard KYN28-12 cabinet features:
- Fully metal armored, assembled structure
- Constructed from imported high-quality zinc-aluminum-deposited steel plate
- CNC machining with advanced folding process
- High precision, corrosion resistance, and lightweight design
- Compliant with GB3906 and IEC298 standards
- 2mm minimum aluminum-zinc coating thickness
- 2.5mm cold rolled steel panel with epoxy resin powder electrostatic spraying
- Supports parallel cabinets with multiple outlet configurations (top/bottom inlet/outlet, busbar connection)
- Standard protection grade: IP40 (customizable)
- Standard color: RAL7035 (customizable)
- Custom sizes available
| Specification | Details |
|---|---|
| Load Type | Three-phase asynchronous motor, synchronous motor |
| Mains Voltage | 3kV-12kVAC -15%-+10 |
| Frequency | 50/60Hz ±2% |
| Power Component | 12SCRs, 18SCRs, 30SCRs |
| Phase Sequence | No phase sequence requirement |
| Circuit Breaker | Handcart type circuit breakers |
| Bypass | HV vacuum contactors with direct starting capacity |
| Instantaneous overvoltage protection | dv/dt absorption network, resistive network |
| Low Voltage Commissioning | With low-voltage test components |
| Fiber Optic Trigger | Fiber optic triggering, complete isolation of high and low voltage components |
| Cooling | Natural cooling |
| Starting frequency | 1-6 times/H |
- Quick-break protection: Circuit breaker 1 section, II section trip protection
- Overcurrent protection: 0-600%Ie,0-60S
- Phase loss protection: Trip protection when main power is out of phase
- Phase break protection: Trip protection for motor phase loss
- Overload protection: 1.05%Ie-10%Ie level protection
- Phase sequence protection: Locking phase sequence of initial installation
- Long starting time protection: Trip if set soft start time is exceeded
- Three-phase power imbalance: 0-100%Ie
- Over-voltage protection: 0-150%Ue
- Undervoltage protection: 0-100%Ue
- Short circuit protection: 0-10%Ie
- Temperature protection: Trip if exceeding set temperature threshold
- Grounding protection: Trip if preset value is exceeded
- Starting curve options: Voltage Ramp, Current Ramp, Current Limit, Fan Consumption Netting
- Starting voltage: 20%-100%Ue
- Current limit: 150%-600%
- Starting time: 1-150S
- Soft stop time: 1-150S
- Pulse start: Pulse voltage 0-100%Ue, pulse time 0-10.00S
- Display: Touch screen human-machine interface showing current, voltage, temperature/humidity, operation status (with data storage)
- Communication Interface: RS-485
- Communication Protocol: Modbus RTU, PROFIBUS-DP
The Anchorwill MT800 series high voltage solid-state soft starting device consists of multiple thyristors in series-parallel configuration. By controlling thyristor trigger angles, it precisely regulates output voltage to meet various motor starting requirements.
During operation, the device follows preset starting curves to gradually increase motor voltage, enabling smooth acceleration while minimizing electrical and mechanical stress on both the motor and power grid. Upon reaching normal speed, a bypass vacuum contactor or circuit breaker engages to complete the starting process.
The system continuously monitors motor performance during operation, providing real-time measurement of current, voltage, and comprehensive fault protection.
Get in Touch