CMF5012 Interface G1/2 Power Supply 8-24 VDC 50mA VDC Optional
CMF5012 Interface G1/2 Power Supply 8~24 VDC, 50 mA VDC Optional
Performance Specifications
Functional Items
| Functional Items | CMF5012 Interface G1/2 Power Supply 8-24 VDC 50mA VDC Optional | Unit | Remarks |
|---|---|---|---|
| Flow Range | 0-50/100/200/300/400 | slpm | Customizable |
| Power Supply | 8~24 VDC, 50 mA | VDC | Optional |
| Accuracy | ±1.5 | % FS | |
| Response Time | 65 (10, 20, 30, 50, 80, 100, 200, etc.) | ms | Customizable |
| Maximum Pressure | 0.8 | MPa | Customizable |
| Communication | RS485 (Modbus) | ||
| Measurement Range | 100:1 | ||
| Output Options | Analog Output 1-5 V | V | Customizable |
| Temperature | Medium Temperature (-10~65) | ℃ | |
| Ambient Temperature (-25~85) | ℃ | ||
| Interface | G1/2 | ||
| Protection Level | IP40 | ||
| Calibration Method | Air, 20℃, 101.325 kPa | ||
| Material | Stainless Steel (Aluminum Alloy Optional) |
Applications
- Industrial
- Medical
- Oil and Gas
- Instrumentation
- Gas Measurement
- Chemical Industry
- Metallurgy
- Food Processing
- Electromechanical Equipment
Product Description
The CMF5012 gas mass flow meter employs a micro-electromechanical system (MEMS) flow sensing chip, making it suitable for various applications involving clean and relatively dry gas flow measurement and process control. Its unique packaging technology accommodates different flow measurement ranges, ensuring high sensitivity, high reliability, high stability, and low cost.
The CMF5012 is based on a MEMS flow sensing unit integrated with a high-precision digital processing and calibration circuit (MCU). The integrated ∆-Σ A/D converter and internal calibration logic circuit, along with the MCU processor, ensure real-time, accurate flow signal acquisition and internal compensation, eliminating the need for external calibration. This guarantees high-precision flow output.
The digital communication output is user-friendly, allowing easy data retrieval through communication interfaces. The CMF5012's wide application range makes it a versatile solution for many industries.
Product Features
- High Accuracy: ±1.5% Full Scale (F.S.) accuracy
- Linear Output: No need for temperature compensation
- Long-term Stability: Maintains minimal zero-drift
- Quick Response Time: 65 ms response time
- Wide Flow Range: 0-60 m/s, impact-resistant up to 100g
- Robust Sensing Core: Solid-state, no surface cavity or fragile film, resistant to blockage and pressure impact
- Output Options: Analog output (1-5 V) with optional RS485 digital communication output
- Adaptability: Suitable for relatively humid gas measurements
- Operating Temperature: -25°C to 85°C
- Storage Temperature: -40°C to 90°C
- Humidity: 0-100% RH
- Condensate Water Resistance: Sensor can withstand condensate water
The CMF5012 gas mass flow meter is designed to provide precise and reliable gas flow measurements, making it an essential tool in various industrial, medical, and environmental applications. Its advanced MEMS technology and robust design ensure high performance and durability.