NS2-25X AC Motor Electric Starter Push Button Type MPCB AC690V 25A Asynchronous Motor
NS2-25X AC Motor Electric Starter Push-Button Type MPCB AC690V 25A Asynchronous Motor
Product Description:
NS2 series AC motor starter is suitable for the circuit of AC voltage to 690V and current to 80A. It is designed for overload, phase failure, short-circuit protection, and infrequent start and control of three-phase squirrel-cage asynchronous motor, The starter can also be used for distribution line protection and infrequent load switching, and can also serve as an isolator.
Product Specification:
| Type | Rated current of release In(A) | Setting current regulation range(A) | Rated ultimate short-circuit breaking lcu Rated service short-circuit breaking capacity lcs kA |
Arcing distance(mm) | |||
| AC 400/415V | AC 690V | ||||||
| lcu | Ics | lcu | lcs | ||||
| NS2-25(X) | 0.16 | 0.1~0.16 | 100 | 100 | 100 | 100 | 40 |
| NS2-25(X) | 0.25 | 0.16~0.25 | 100 | 100 | 100 | 100 | 40 |
| NS2-25(X) | 0.4 | 0.25~0.4 | 100 | 100 | 100 | 100 | 40 |
| NS2-25(X) | 0.63 | 0.4~0.63 | 100 | 100 | 100 | 100 | 40 |
| NS2-25(X) | 1 | 0.63~1 | 100 | 100 | 100 | 100 | 40 |
| NS2-25(X) | 1.6 | 1~1.6 | 100 | 100 | 100 | 100 | 40 |
| NS2-25(X) | 2.5 | 1.6~2.5 | 100 | 100 | 3 | 2.25 | 40 |
| NS2-25(X) | 4 | 2.5~4 | 100 | 100 | 3 | 2.25 | 40 |
| NS2-25(X) | 6.3 | 4~6.3 | 100 | 100 | 3 | 2.25 | 40 |
| NS2-25(X) | 10 | 6~10 | 100 | 100 | 3 | 2.25 | 40 |
| NS2-25(X) | 14 | 9~14 | 15 | 7.5 | 3 | 2.25 | 40 |
| NS2-25(X) | 18 | 13~18 | 15 | 7.5 | 3 | 2.25 | 40 |
| NS2-25(X) | 23 | 17~23 | 15 | 6 | 3 | 2.25 | 40 |
| NS2-25(X) | 25 | 20~25 | 15 | 6 | 3 | 2.25 | 40 |
| NS2-32(X) | 32 | 24~32 | 10 | 5 | 3 | 2.25 | 40 |
| NS2-32H | 0.16 | 0.1~0.16 | 100 | 100 | 100 | 100 | 40 |
| NS2-32H | 0.25 | 0.16~0.25 | 100 | 100 | 100 | 100 | 40 |
| NS2-32H | 0.4 | 0.25~0.4 | 100 | 100 | 100 | 100 | 40 |
| NS2-32H | 0.63 | 0.4~0.63 | 100 | 100 | 100 | 100 | 40 |
| NS2-32H | 1 | 0.63~1 | 100 | 100 | 100 | 100 | 40 |
| NS2-32H | 1.6 | 1~1.6 | 100 | 100 | 100 | 100 | 40 |
| NS2-32H | 2.5 | 1.6~2.5 | 100 | 100 | 4 | 4 | 40 |
| NS2-32H | 4 | 2.5~4 | 100 | 100 | 4 | 4 | 40 |
| NS2-32H | 6.3 | 4~6.3 | 100 | 100 | 4 | 4 | 40 |
| NS2-32H | 10 | 6~10 | 100 | 100 | 4 | 4 | 40 |
| NS2-32H | 14 | 9~14 | 50 | 25 | 4 | 4 | 40 |
| NS2-32H | 18 | 13~18 | 50 | 25 | 4 | 4 | 40 |
| NS2-32H | 23 | 17~23 | 50 | 25 | 4 | 4 | 40 |
| NS2-32H | 25 | 20~25 | 50 | 25 | 4 | 4 | 40 |
| NS2-32H | 32 | 24~32 | 50 | 25 | 4 | 4 | 40 |
| NS2-80 | 25 | 20~25 | 50 | 17.5 | 4 | 2 | 50 |
| NS2-80 | 32 | 23~32 | 50 | 17.5 | 4 | 2 | 50 |
| NS2-80 | 40 | 30~40 | 50 | 17.5 | 4 | 2 | 50 |
| NS2-80 | 50 | 37~50 | 50 | 17.5 | 4 | 2 | 50 |
| NS2-80 | 65 | 48-65 | 50 | 17.5 | 4 | 2 | 50 |
| NS2-80 | 80 | 63-80 | 50 | 17.5 | 4 | 2 | 50 |
Operating Conditions and Environmental Suitability:
•Altitude: ≤ 2000m.
•Ambient Air Temperature: -5℃~+40℃, with daily average≤ +35℃.
•Relative Humidity: ≤ 90% (at +25°C ±5°C).
•Pollution Degree: 3.
•Installation Category: III.
•Installation Angle: The tilt angle of the starter with respect to the vertical plane should not exceed ±5°.
•Tripping Class: NS2-25(X), NS2-32(X), NS2-32H, NS2-80: 10A.
•Rated Operating System: Continuous duty, eight-hour duty.
FAQ:
Q: How can i get the price?
A: We usually quote within 24 hours after we get your inquiry(Except weekend and holidays). If you are very urgent to get the price, please email us or contact us in other ways so that we can offer you a quote.
Q:How could I get a sample?
A:Before we received the first order, please afford the sample cost and express fee. We will return the sample cost back to you within your first order.
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.