BS6387 Fire Resistance Tester for LSZH and MICC Cables
The BS 6387:2013 Cable Fire Resistance, Hammer and Spray Tester is a comprehensive testing system designed to evaluate circuit integrity of fire-resistant cables under extreme conditions. This all-in-one machine performs three critical tests (CWZ) to ensure cables maintain functionality during fires.
Key Testing Capabilities
Category C - Fire Resistance Test
  • 950°C ± 40°C propane flame for 3 hours
  • Tests cable circuit integrity under sustained high temperature
  • Ensures no short circuits or breaks during extended fire exposure
Category W - Fire and Water Spray Test
  • 650°C ± 40°C flame for 15 minutes + water spray for 15 minutes
  • Water spray rate: 0.25-0.30 L/m²/s
  • Simulates fire sprinkler system activation scenarios
Category Z - Fire and Mechanical Impact Test
  • 950°C ± 40°C flame for 15 minutes
  • Mechanical impact every 30 seconds using 25mm steel rod
  • Tests cable durability under physical stress during fires
Technical Specifications
Applicable Cables: Rated voltage ≤ 600/1000 V, diameter ≤ 20 mm (including LSZH and MICC cables)
Test Voltage: 0-1000V continuously adjustable
Current Rating: 0.25A per conductor
Burner Specifications: 500-610 mm propane burner with venturi mixer
Temperature Measurement: K-type thermocouple with Φ1.5mm mineral insulated stainless steel sheath
Control System: PLC with touch screen interface, automatic data collection and reporting
Compliance and Standards
This equipment is designed in accordance with BS 6387:2013 and supports testing for multiple international standards:
Standard Application Key Parameters
BS 6387:2013 Primary reference standard for comprehensive fire, impact, and spray testing 950°C flame (C/Z), 650°C flame (W)
IEC 60331 International standard for circuit integrity under fire conditions 750-830°C flame temperature
EN 50200 European standard for emergency circuit cables 830°C flame with mechanical impacts
SS 299:2021 Singapore standard equivalent to BS 6387 Same test conditions as BS 6387
BS 8491:2008 For cables with diameter > 20 mm 850°C flame with mechanical shock and water jet
Test Equipment Components
  • 500-610 mm propane burner assembly
  • Mechanical impact device with 25mm steel rod
  • Programmable sprinkler system
  • Sample support device with 3 wire support rings (150mm inner diameter)
  • Continuity check system with 2A fuses
  • K-type thermocouple temperature monitoring
  • PLC control system with touch screen interface
Application Areas
This testing equipment is essential for cable manufacturers and certification bodies working with:
  • Fire alarm and detection systems
  • Emergency lighting and power circuits
  • Public broadcasting and communication systems
  • High-rise buildings, hospitals, and public infrastructure
  • Transportation systems (railways, metro, airports)
  • Marine and offshore emergency circuits
BS6387 Fire Resistance Tester showing complete testing setup with burner, controls, and sample mounting Water and fire resistance test configuration with sprinkler system and cable samples Mechanical vibration and fire resistance test setup showing impact mechanism and burner assembly

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Chongqing gold mechnical and electrical equipment Co., Ltd
Location 25F, China Resources Building, Xiejiawan, Jiulongpo District,Chongqing,400050,China
Contact Person Ivy Zhang

Request A Quote

Please check your email address.
Your message must be at least 20 characters.