Lightning Protection 3 Phase AC Whole House Surge Protectors 220V 20kA 40kA T2 SPD

|
Benefits
|
||
|
|
|
|
Applications

Product Specification
| Standards | IEC 61643.11 |
| SPD type | T2 |
| Models | LPX-40C, LPX-80C |
| Nominal operating voltage Un | 220Vac(50Hz) |
| Maximum continuous operating voltage Uc | 385Vac(50Hz) |
| Nominal discharge current (8/20μs) In | 20kA, 40kA |
| Maximum discharge current (8/20μs) Imax | 40kA, 80kA |
| Voltage protection level Up | ≤1.25kV, ≤1.8kV |
| Response time tA | ≤25ns |
| Protection Circuit | L1,L2,L3-N,N-E |
| Lightning stroke range | 0.9kA(8/20μs)~80kA(8/20μs) |
| Counting digit | 0~999 |
Mechanical Parameters
| Installation method | 4 fixed holes, DIN Rail 35mm |
| Screw torque | 5N·m |
| Strip length | 12mm |
| Wiring cross-sectional area | 2.5mm²~10mm² |
| Product size | 178mm×116mm×75mm, 197mm×139mm×90mm |
| Shell material and surface technology | Cold rolled steel plate painted black |
| Alarm system - Deterioration indication | LED green: OK; Off: Fail |
| Remote signaling contact type | Normally closed and normally open switching contacts |
| Remote signaling contact switching ability | 125Vac / 1A, 125Vdc / 0.2A |
| Maximum connection capacity of remote signaling | 2.5mm² |
1.Install the lightning protection box in a dry, well-ventilated indoor environment, and keep it away from flammable materials.
2.Use wires with a cross-sectional area of 2.5mm²~10mm², and tighten the screws to a torque of 5N·m.
3.Ensure reliable earthing, with a ground resistance ≤4Ω, to achieve optimal surge discharge effect.
4.Regularly check the lightning count and status indicator: if the product fails, the indicator will turn off. Replace the faulty device in a timely manner.
5.Do not connect the product to a power supply that exceeds its rated voltage and current.
6.Avoid using the product beyond the specified temperature and humidity ranges.
FAQ
A1: The counter can record lightning strikes with a discharge current ranging from 3kA(8/20μs) to 80kA(8/20μs), with a digital display range of 0 to 999.
A2: Yes. It is equipped with normally closed and normally open remote signaling contacts, allowing connection to a monitoring system for remote status tracking.
A3: The core difference lies in the maximum discharge current (Imax): LPX-40C has an Imax of 40kA, while LPX-80C has an Imax of 80kA, making them suitable for different system protection requirements.
A4: No. This product is designed for indoor use only. For outdoor applications, please select products with an IP67 protection level.
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.