SLASXCV2 Schneider SpaceLogic SLA CO2 VOC RH Temp Analog Blank White

Price Negotiable
Price: Negotiable
MOQ: 5
Delivery Time: 7 Days
Brand: Schneider
Product Description
SLASXCV2 Schneider SpaceLogic SLA CO2 VOC RH Temp Analog Blank White
Product Overview

The Schneider Electric SLASXCV2 is a 4-in-1 analog room air quality sensor from the SpaceLogic SLA Series, designed for seamless integration with legacy BMS controllers and stand-alone HVAC systems that utilize standard analog signals (4-20mA, 0-5V, or 0-10V).

This sensor measures CO2, VOC, Relative Humidity, and Temperature, providing essential data for demand-controlled ventilation in a tamper-resistant medium white matte housing without a user interface. It's the standard choice for building retrofits where a high-performance multisensor is required to replace aging single-function analog sensors without the complexity of a full communication bus upgrade.

Technical Specifications
Part Number SLASXCV2
Series SpaceLogic SLA Analog Series
Output Types Field-selectable 4-20mA, 0 to 5 V DC, or 0 to 10 V DC
Integrated Sensors CO2, VOC, Humidity, Temperature
CO2 Measurement Range 0 to 2000/5000 ppm (selectable)
CO2 Accuracy +/- 30 ppm +/- 3% of reading
VOC Range 0 to 100% AQI
Humidity Accuracy +/- 2% RH
Temperature Accuracy +/- 0.5 degC over full range
Power Supply 24 V AC / 20 to 30 V DC
Number of Outputs 1 dedicated + 1 configurable analog
Housing Medium Matte White, Blank cover
Dimensions 115 x 85 x 24 mm
Certifications UL 916, CE, RCM, ICES-003, CULus
Application Scenarios

The SLASXCV2 is specified for HVAC modernization projects where existing DDC controllers require high-density air quality data but do not support BACnet or Modbus communications. By providing four measurement parameters via selectable analog signals, it allows engineers to implement modern IAQ control sequences in older facilities.

Its blank cover design is standard for commercial restrooms, storage closets, and secondary hallways where reliable monitoring is needed without occupant-accessible displays or adjustment buttons.

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Maituo Intelligent Technology Co.,Ltd
Location 1st Floor, Building 4, Xindao Street, Yazhou District, Sanya City, Hainan Province, China
Contact Person Nora

Request A Quote

Please check your email address.
Your message must be at least 20 characters.