Maituo Intelligent Technology Co.,Ltd
                                                                                                           
Verified Supplier
7 Years
Since 2019
Menu

HD5XMSTH Schneider Duct Probe Humidity Temperature Transmitter Economy Grade 4-20mA 10k Thermistor

Price Negotiable
Price: Negotiable
MOQ: 5
Delivery Time: 7 Days
Brand: Schneider
Product Description
HD5XMSTH Schneider Duct Probe Humidity Temperature Transmitter Economy Grade 4-20mA 10k Thermistor
Product Overview

The HD5XMSTH is a duct-mounted temperature and humidity transmitter designed for HVAC applications. This economy grade device is ideal for volume applications where large air handling units require air condition monitoring without the expense of instrument grade sensors.

It measures both relative humidity and temperature using a single probe inserted into the duct, requiring only one penetration and one cable for both readings. The humidity element features a thin film capacitive type that remains stable over time and recovers effectively from saturation events. Temperature measurement is provided by a 10kΩ type 3 thermistor, compatible with Schneider controllers as standard. The humidity channel delivers a current output that universal inputs can accept directly without signal conditioning.

Specifications
Parameter Detail
Product type Duct mounted humidity and temperature transmitter
Order number HD5XMSTH
Grade Economy grade, intended for high volume HVAC applications
Mounting Duct mount, probe inserted through the duct wall
Humidity element Thin film capacitive sensing element
Humidity output 4 to 20 mA current signal
Humidity accuracy Approximately 5 percent relative humidity
Temperature element 10 kOhm type 3 thermistor
Temperature output Resistance output read directly by the controller input
Compatibility Suitable for Schneider building controllers with universal inputs
Measured media Air in supply, return and mixed air ducts
Installation Probe inserted into the duct with the housing outside
Compliance CE marking; RoHS and REACH declarations held by Schneider Electric
System Integration Notes

Proper sensor positioning is critical for accurate measurements. In humidification or cooling coil applications, the choice between upstream and downstream measurement significantly impacts reading interpretation:

  • Upstream measurement indicates load conditions
  • Downstream measurement shows results
  • Using incorrect positioning can create conflicting control loops

Stratification is another important consideration. Probes placed in short ducts immediately after coils or fans may encounter unrepresentative air mixtures. The practical solution is to position measurements in straight sections with adequate distance from disturbances.

The capacitive humidity element is vulnerable to contamination from dust and aerosols. Maintain filters or sintered caps in place and keep the probe away from direct spray from upstream washers. Current output and resistive temperature elements are calibrated at the controller, requiring proper scaling alignment with actual ranges rather than default templates.
Application Scenarios

This transmitter is primarily used in air handling units where supply and return humidity measurements control humidification, dehumidification, and coil capacity:

  • Return air measurement: Establishes plant load conditions
  • Mixed air measurement: Sets economiser thresholds
  • Cleanrooms and laboratories: Supports room condition monitoring
  • Hospitals: Operating theatre and isolation plant humidity control
  • Swimming pools and leisure centres: Condensation control and building protection
  • Commercial offices: Drives economiser and ventilation strategies based on conditions rather than fixed schedules

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Maituo Intelligent Technology Co.,Ltd
Location 1st Floor, Building 4, Xindao Street, Yazhou District, Sanya City, Hainan Province, China
Contact Person Nora

Request A Quote

Please check your email address.
Your message must be at least 20 characters.