Industrial Current Transducer LEM LXS 15-NPS with LTS Footprint Compatibility and Galvanic Isolation
LXS Series Current Transducer
The LXS series are closed-loop multi-range current transducers with voltage output, designed for the electronic measurement of DC, AC, and pulsed currents. They provide galvanic separation between the primary and secondary circuits. Key advantages include very low offset drift, high dv/dt immunity, LTS footprint compatibility, and an extended measuring range for unipolar measurement. These transducers are ideal for applications such as AC variable speed and servo motor drives, static converters for DC motor drives, battery supplied applications, Uninterruptible Power Supplies (UPS), Switched Mode Power Supplies (SMPS), power supplies for welding applications, and solar inverters. They are suitable for industrial application domains.
Product Attributes
- Brand: LEM
- Certifications: UL 508, CSA C22.2 NO. 14-10, IEC 61800 series, IEC 62109-1, IEC 62477-1
- Application Domain: Industrial
Technical Specifications
| Parameter | Symbol | Unit | LXS 6-NPS (Min) | LXS 6-NPS (Typ) | LXS 6-NPS (Max) | LXS 15-NPS (Min) | LXS 15-NPS (Typ) | LXS 15-NPS (Max) | LXS 25-NPS (Min) | LXS 25-NPS (Typ) | LXS 25-NPS (Max) | Comment |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Primary nominal RMS current | IP N | A | - | 6 | - | - | 15 | - | - | 25 | - | Apply derating according to fig. 16, 17, 18 |
| Primary current, measuring range | IP M | A | -20 | - | 20 | -51 | - | 51 | -85 | - | 85 | |
| Supply voltage | UC | V | 4.75 | 5 | 5.25 | 4.75 | 5 | 5.25 | 4.75 | 5 | 5.25 | |
| Output voltage @ IP = 0 A | Vout | V | - | 2.5 | - | - | 2.5 | - | - | 2.5 | - | |
| Electrical offset voltage | VO E | mV | -15 | - | 15 | -13 | - | 13 | -11 | - | 11 | 100 % tested |
| Temperature coefficient of Vout @ IP = 0 A | TCVout | ppm/K | - | 70 | - | - | 80 | - | - | 80 | - | ppm/K of 2.5 V, -40 C ... 105 C |
| Theoretical sensitivity | Gth | mV/A | - | 104.2 | - | - | 41.67 | - | - | 25 | - | 625 mV/ IP N |
| Sensitivity error | G | % | -0.2 | - | 0.2 | -0.2 | - | 0.2 | -0.2 | - | 0.2 | 100 % tested |
| Temperature coefficient of G | TCG | ppm/K | - | 45 | - | - | 45 | - | - | 45 | - | -40 C ... 105 C |
| Linearity error | L | % of IP N | -0.1 | - | 0.1 | -0.1 | - | 0.1 | -0.1 | - | 0.1 | |
| Reaction time @ 10 % of IP N | tra | s | - | 0.3 | - | - | 0.3 | - | - | 0.3 | - | RL = 1 k, di/dt = 50 A/s |
| Step response time to 90 % of IP N | tr | s | - | 0.4 | - | - | 0.4 | - | - | 0.4 | - | RL = 1 k, di/dt = 50 A/s |
| Frequency bandwidth (3 dB) | BW | kHz | - | 300 | - | - | 300 | - | - | 300 | - | RL = 1 k |
| Overall accuracy | XG | % of IP N | - | 2.25 | - | - | 1.6 | - | - | 1.8 | - | |
| Accuracy | X | % of IP N | - | 0.5 | - | - | 0.5 | - | - | 0.5 | - | |
| Ambient operating temperature | TA | C | -40 | - | 105 | -40 | - | 105 | -40 | - | 105 | |
| Ambient storage temperature | TS | C | -55 | - | 125 | -55 | - | 125 | -55 | - | 125 | |
| Mass | m | g | - | 10 | - | - | 10 | - | - | 10 | - |
Get in Touch