TAG-8600C Wireless High Voltage Phase Detector

The TAG-8600C Wireless High Voltage Phase Detector is designed for phase verification in grid connection and ring network operations of high-voltage transmission lines.

It supports phase comparison of AC transmission lines ranging from 5V to 500kV and can also be used for live line detection and phase sequence verification in power systems.

With advanced wireless communication technology, the device eliminates the limitations of traditional wired phase detectors, providing safer, more stable, and more convenient field operation.


Working Principle

The system consists of two transmitters and one receiving host:

  • The transmitters detect line voltage status, phase, and frequency

  • Data is transmitted wirelessly to the receiving host

  • The host calculates phase difference between X and Y lines

  • The system determines in-phase or out-of-phase condition

X line is used as reference, and Y phase is calculated relative to X.


Key Features
  • Suitable for 5V–500kV AC transmission line testing

  • Wireless communication between transmitters and receiver

  • Supports phase verification, phase sequence detection, and live line detection

  • Voice prompts for operation and result guidance

  • 3.2-inch color screen with vector diagram display

  • Automatic in-phase / out-of-phase judgment system

  • High-voltage isolation design for safety operation

  • Built-in rechargeable lithium battery system

  • Auto power-off after 1 hour inactivity

  • Lightweight portable design for field testing


Applications
  • High voltage transmission line phase verification

  • Grid connection and ring network operation

  • Substation phase sequence testing

  • Power system commissioning and maintenance

  • Generator synchronization preparation

  • Live line safety inspection


Technical Specifications
Item Specification
Phase Difference Accuracy ≤ ±5°
Frequency Accuracy ±0.1 Hz
Voltage Measurement Range 5V – 500kV AC
Wireless Transmission Distance ≤ 100 m
Display 3.2-inch color screen
Judgment Threshold ±30°
Host Battery 2600mAh lithium battery
Transmitter Battery 340mAh lithium battery
Power Consumption <0.3W (host), <0.1W (transmitter)
Operating Temperature -35℃ ~ +45℃
Humidity ≤95% RH
Total Weight ~7 kg

Result Judgment Logic
  • Phase difference ≥ ±30° → Out-of-phase

  • Phase difference < ±30° → In-phase

Voice prompts, screen display, and indicator lights provide real-time confirmation.


Important Notice

If the frequency of the two lines is inconsistent, synchronization adjustment must be completed before grid connection. Power transmission is only allowed when both phase and frequency match the main grid.


Reliable Supply & Service Support
  • Language Customization Available
    Software interface, manuals, and labeling can be customized for different markets.

  • 2-Year Warranty & Technical Support
    All products are supplied with 2-year warranty and professional after-sales support.

  • Strict Quality Control
    Each unit is tested before shipment to ensure accuracy, safety, and reliability.

  • OEM & Customization Available
    Functional and structural customization supported according to customer requirements.


FAQ
What is a high voltage phase detector used for?

It is used to verify phase consistency between high-voltage transmission lines before grid connection or ring network operation.


What voltage range can this device measure?

It supports AC transmission line phase detection from 5V to 500kV.


Can this device be used for live line testing?

Yes, it supports live line detection and is designed for safe field operation.


Does it support wireless operation?

Yes, it uses wireless communication between transmitters and the receiving host.


What is the purpose of phase difference judgment?

It determines whether two lines are in-phase or out-of-phase to ensure safe grid connection.


Is customization available?

Yes, OEM customization, language localization, and parameter adjustments are available.


Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Wuhan HKV test Electrical Equipment Manufacturing Co., Ltd
Location Room 403, Unit 4-02, Phase III, Optics Valley Core Center, No. 303 Guanggu Avenue, East Lake High-Tech Development Zone, Wuhan City, Hubei Province, P.R.China
Contact Person fiona

Request A Quote

Please check your email address.
Your message must be at least 20 characters.