Product Description
2-Wire HART Transmitter PR 5335DRTD
Product Overview
- 2-wire transmitter with HART 5 protocol
- TC, Ohm, or mV input compatibility
- Extremely high measurement accuracy
- Galvanic isolation
- Designed for DIN form B sensor head mounting
Environmental Conditions
| Operating temperature | -40°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-condensing) |
| Protection degree (enclosure/terminal) | IP68 / IP00 |
Mechanical Specifications
| Dimensions | Ø 44 x 20.2 mm |
| Weight approx. | 50 g |
| Wire size | 1 x 1.5 mm² stranded wire |
| Screw terminal torque | 0.4 Nm |
| Vibration (IEC 60068-2-6) | 2...25 Hz: ±1.6 mm 25...100 Hz: ±4 g |
Common Specifications
| Supply voltage | 8.0...30 VDC |
| Isolation voltage (test/working) | 1.5 kVAC / 50 VAC |
| Response time (programmable) | 1...60 s |
| Warm-up time | 30 s |
| Programming | HART & PR 5909 Loop Link communications interface |
| Signal / noise ratio | > 60 dB |
| Accuracy | Better than 0.05% of selected range |
| Signal dynamics, input | 22 bit |
| Signal dynamics, output | 16 bit |
| Effect of supply voltage change | < 0.005% of span / VDC |
| EMC immunity influence | < ±0.1% of span |
| Extended EMC immunity (NAMUR NE21) | < ±1% of span |
Input Specifications
Common Input Specifications
| Maximum offset | 50% of selected maximum value |
RTD Input
| RTD type | Pt100, Ni100, linear R |
| Cable resistance per wire | 5 Ω (up to 50 Ω per wire possible with reduced accuracy) |
| Sensor current | Nominal 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Yes |
TC Input
| Thermocouple type | B, E, J, K, L, N, R, S, T, U, W3, W5 |
| Cold junction compensation (CJC) | < ±1.0°C |
| Sensor error detection | Yes |
| Sensor error current (when detecting/else) | Nominal 33 μA / 0 μA |
Voltage Input
| Measurement range | -800...+800 mV |
| Minimum measurement range (span) | 2.5 mV |
| Input resistance | 10 MΩ |
Output Specifications
| Signal range | 4…20 mA |
| Minimum signal range | 16 mA |
| Load (@ current output) | ≤ (Vsupply - 8) / 0.023 [Ω] |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Sensor error indication | Programmable 3.5…23 mA |
| NAMUR NE43 Upscale/Downscale | 23 mA / 3.5 mA |
Intrinsic Safety & Explosion Protection Marking
| ATEX | II 1 G Ex ia IIC T6...T4 Ga, II 2 D Ex ia IIIC Db, I M1 Ex ia I Ma |
| IECEx | Ex ia IIC T6...T4 Ga, Ex ia IIIC Db, Ex ia I Ma |
| FM, US | Cl. I, Div. 1, Gp. A, B, C, D T4/T6; Cl. I Zone 0, AEx ia IIC T4/T6; Cl. 1, Div. 2, Gp. A, B, C, D, T4/T6 |
| CSA | Cl. I, Div. 1, Gp. A, B, C, D Ex ia IIC, Ga |
| INMETRO | Ex ia IIC T6...T4 Ga, Ex ia IIIC Db, Ex ia I Ma |
Compliance with Authority Requirements
| EMC | 2014/30/EU |
| ATEX | 2014/34/EU |
| RoHS | 2011/65/EU |
| EAC | TR-CU 020/2011 |
| EAC Ex | TR-CU 012/2011 |
Approvals and Certifications
| ATEX | DEKRA 20ATEX0108X |
| IECEx | DEK 20.0063X |
| FM | FM17US0013X |
| CSA | 1125003 |
| INMETRO | DEKRA 23.0011X |
| EAC Ex | EAEU KZ 7500361.01.01.08756 |
| DNV Marine | TAA0000101 |
| SIL | Hardware assessed for use in SIL applications |