PR 9116A Universal Signal Converter RTD TC Ohm mA V Input 4-20mA 0-10V Output DIN Rail Mount
Price:
150-350usd
MOQ:
1
Delivery Time:
5-7 work days
Brand:
PR
Product Description
Universal Converter PR 9116A
Input for RTD, TC, Ohm, potentiometer, mA and V • Supply for 2-wire transmitters • Active/passive mA output and relay output
Product Overview
The PR 9116A Universal Converter is a versatile signal conditioning device designed for industrial applications. It accepts multiple input types and provides reliable signal conversion with flexible output options. The unit can be supplied separately or installed on DIN rail systems.
Environmental Specifications
| Operating temperature | -20°C to +60°C |
| Storage temperature | -20°C to +85°C |
| Calibration temperature | 20...28°C |
| Relative humidity | < 95% RH (non-condensing) |
| Protection degree | IP20 |
| Installation environment | Pollution degree 2 & measurement/overvoltage category II |
Mechanical Specifications
| Dimensions (H*W*D) | 109 * 23.5 * 104 mm |
| Dimensions with PR 4500 | 109 * 23.5 * 131 mm |
| Weight (approx.) | 185 g |
| DIN rail type | DIN EN 60715/35 mm |
| Wire size | 0.13...2.08 mm² AWG 26...14 stranded wire |
| Stripping length | 5 mm |
| Screw terminal torque | 0.5 Nm |
| Vibration resistance | IEC 60068-2-6 compliant |
Electrical Specifications
Power Supply
| Supply voltage | 19.2...31.2 VDC |
| Fuse | 1.25 A SB / 250 VAC |
| Maximum required power | ≤ 2.1 W |
| Maximum power dissipation | ≤ 1.7 W |
Isolation Voltage
| Input to any (test/working) | 2.6 kVAC / 300 VAC reinforced isolation |
| Analog output to supply | 2.6 kVAC / 300 VAC reinforced isolation |
| Status relay to supply | 1.5 kVAC / 150 VAC reinforced isolation |
Performance Characteristics
| Response time (temperature input) | 1...60 s (programmable 0...90%, 100...10%) |
| Response time (mA/V input) | 0.4...60 s (programmable) |
| Signal dynamics (input) | 24 bit |
| Signal dynamics (output) | 16 bit |
| Signal/noise ratio | Minimum 60 dB (0...100 kHz) |
| Accuracy | Better than 0.1% of selected range |
Input Specifications
RTD Input
| RTD types supported | Pt10/20/50/100/200/250; Pt300/Pt400/500/1000; Ni50/100/120/1000 |
| Cable resistance per wire | 50 Ω (maximum) |
| Sensor current | Nominal 0.2 mA |
| Effect of sensor cable resistance (3-/4-wire) | < 0.002 Ω / Ω |
| Sensor error detection | Programmable ON / OFF |
| Short circuit detection | Yes |
Thermocouple Input
| Thermocouple types | B, E, J, K, L, N, R, S, T, U, W3, W5, LR |
| Cold junction compensation (external sensor) | 20...28°C ≤ ±1°C, -20...20°C / 28...70°C ≤ 2°C |
| Cold junction compensation (internal sensor) | ±(2.0°C + 0.4°C * Δt) |
| Sensor error detection | Programmable ON or OFF (wire breakage only) |
Current and Voltage Inputs
| Current measurement range | 0...23 mA |
| Programmable current ranges | 0...20 and 4...20 mA |
| Current input resistance | Nominal 20 Ω + PTC 50 Ω |
| Voltage measurement range | 0...12 VDC |
| Programmable voltage ranges | 0/0.2...1, 0/1...5, 0/2...10 VDC |
| Voltage input resistance | Nominal >10 MΩ |
Output Specifications
Current Output
| Signal range | 0...23 mA |
| Programmable signal ranges | 0...20/4...20/20...0/20...4 mA |
| Load (@ current output) | ≤ 600 Ω |
| Load stability | ≤ 0.01% of span / 100 Ω |
| Current limit | ≤ 28 mA |
Relay Output
| Relay functions | Setpoint, Window, Sensor error, Power and Off |
| Maximum voltage | 250 VAC / VDC |
| Maximum current | 2 A |
| Maximum AC power | 500 VA |
Certifications and Approvals
| EMC | 2014/30/EU & UK SI 2016/1091 |
| LVD | 2014/35/EU & UK SI 2016/1101 |
| RoHS | 2011/65/EU & UK SI 2012/3032 |
| ATEX | 2014/34/EU & UK SI 2016/1107 |
| ATEX Approval | KEMA 10ATEX0053 X |
| IECEx | KEM 10.0022X |
| UKEX | DEKRA 21UKEX0177X |
| FM US/Canada | FM19US0058X / FM19CA0031X |
| INMETRO | DEKRA 23.0006X |
| UL 61010-1 | E314307 |
| UL 913 | E233311 (only 9116xx-U9) |
| CCC | 2024322316005917 |
| KCs | 21_AV4BO_0178X (only 9116Ax-KCs) |
| EAC Ex | EAEU KZ 7500361.01.01.08756 |
| DNV Marine | TAA00000JD |
| ClassNK | TA24034M |
| SIL | SIL 2 certified & fully assessed according to IEC 61508 |
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Shaanxi Qindiyuan Environmental Protection Equipment Co., Ltd.
Location
F1-803, Guorun Silu Jin Rong Zhongxin, Qindu District, Xianyang City, Shaanxi Province
Contact Person
Leon