ODM R22 Ultra Low Temperature Recirculating Chillers Anti Corrosion Water Cooler
Stable Circulation Low Temperature Water Chiller Anti-corrosion Shell For Electroplating Process
Ensure flawless finishes and consistent plating quality with our Stable Circulation Low Temperature Chiller. Engineered specifically for the aggressive environment of electroplating and metal finishing, this unit features a heavy-duty anti-corrosion shell and a precision low-temperature control system. It delivers stable, chilled water as low as -10°C directly to your plating baths, anodizing tanks, and rectifiers. By maintaining exact solution temperatures, our chiller prevents burning, improves deposit uniformity, and dramatically reduces rejects—all while surviving the harsh realities of acid mist and chemical fumes.
| Model/Watertemperature | HLS-3A-LT | HLS-4A-LT | HLS-5A-LT | HLS-8A-LT | HLS-10A-LT | HLS-15A-LT | HLS-20A-LT | HLS-25A-LT | HLS-30A-LT | HLS-40A-LT | |
| Cooling capacity (KW) (low temperature unit) |
0 | 6.1 | 8.3 | 10.6 | 17 | 20.8 | 27.3 | 43.2 | 52.5 | 64.8 | 86 |
| -5 | 5.05 | 8.95 | 8.55 | 13.9 | 17.2 | 22.1 | 36.3 | 40.6 | 54.5 | 70.2 | |
| -10 | 4.25 | 5.7 | 7.2 | 11.4 | 14.25 | 17.6 | 28.6 | 31.8 | 43.2 | 57.9 | |
| -15 | 3.5 | 4.65 | 5.9 | 9.2 | 10.8 | 14.3 | 22.2 | 24.4 | 34.3 | 45.2 | |
| Cooling capacity (KW) (ultra-low temperatu re unit)) |
-20 | 4.64 | 5.89 | 7.03 | 8.39 | 10.28 | 16.7 | 19.88 | 24.9 | 29.3 | 32.8 |
| -25 | 3.59 | 4.54 | 5.52 | 6.43 | 7.76 | 12.74 | 15.32 | 19.02 | 22.6 | 25.2 | |
| -30 | 2.71 | 3.42 | 4.09 | 4.8 | 5.68 | 9.41 | 11.47 | 14.09 | 16.91 | 18.83 | |
| -35 | 1.99 | 2.5 | 2.99 | 3.47 | 3.99 | 6.62 | 8.26 | 10 | 12.18 | 13.46 | |
| -40 | 1.41 | 1.76 | 2.1 | 2.39 | 2.62 | 4.33 | 5.62 | 6.65 | 8.27 | 8.99 | |
| Power | Volt | 3P-380/415V-50/60HZ | |||||||||
| Refrigerant | Type | R22/R404a/R407c | |||||||||
| Control Method |
External equalizer thermal expansion valve | ||||||||||
| Compressor | Type | Scroll or Piston | |||||||||
| Power | 2.25 | 3 | 3.75 | 5 | 7.5 | 11 | 15 | 18.75 | 22.5 | 30.1 | |
| CoolingAir Volume |
m3/h | 3400 | 4500 | 5600 | 8800 | 11000 | 16000 | 21000 | 26000 | 32000 | 43000 |
| Inlet Outlet PipeDiameter | 3/4- | 3/4" | 1" | 1-1/2" | 1-1/2" | 2" | 2" | 2-1/2" | 2-1/2" | 3" | |
| ChilledWaterFlow | 1.5 | 2 | 2.5 | 5 | 5 | 7.5 | 10 | 12.5 | 15 | 21.2 | |
| Dimensions | Length(L) | 1070 | 1070 | 1165 | 1540 | 1540 | 1780 | 2030 | 2580 | 2580 | 2030 |
| Width(W) | 600 | 600 | 680 | 780 | 780 | 830 | 910 | 910 | 910 | 1800 | |
| Height(H) | 1370 | 1370 | 1540 | 1690 | 1690 | 1750 | 1925 | 2020 | 2020 | 2000 | |
| weight (Kg) | 170 | 250 | 270 | 370 | 520 | 790 | 880 | 1100 | 1280 | 1420 | |
Project Case
A3: Yes, warm welcome customers to visit our workshop and test equipment on site. We support live video factory tour if you cannot come to China temporarily.
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.