Airport installation modular AHUs with KRUGER fan VFD max 800 tons
EK keeps looking for valuable distributors and partners around international markets…
Airport installation modular AHUs with KRUGER fan VFD max 800 tons
PUFOAM insulation thickness :30/50mm
External sheet : 0.5 mm preplasticized steel standard , 1 mm is optional
Internal sheet : 0.5 mm Galvanised steel standard , 1 mm is optional
Aluminum frame
Base height : 50 mm /80 mm
Sections : Mixing section,Prefilter section,Medium filter section ,HEPA Filter section ,Cooling coil section,Heating coil section , Wet film humidifier / Elec trode humidifier / steam humidifier / HP Atomizing humidifier /Electric heater humidifier section ,Electric heater section , Fan section ,Diffusion section ,muffler section
Heat recovery wheel section , Plate heat recovery section ,Access door section
Mixing section: Return air damper ,Fresh air damper
Prefilter : Nylon ,panel G3/G4 ,Bag G3/G4
Medium filter : F5,F6,F7,F8
HEPA Filter :H10,H11,H13
Pressure swich & gauge are optional
Access door section : light & window are optinal
Cooling coil : Row 2 3 4 5 6 8 10 12; Aluminum fins : 11 12 13 14 15 16 FPI
Heating coil : Row 1 2 3 4 ; Aluminum fins : 11 12 13 14 15 16 FPI
Drain Pan :Zinc Painting Steel;SS304 is optional
Hydrophilic Aluminum fins is optional
Supply fan :Yilida/Kruger , backward/forward centrifugal type standard , plug fan is optional
Motor : ABB,SIEMENS,Chinese Brand, variable frequency motor is optional
TEFC/IP55/F TEFC/IP54/F
VFD & start cabinet are optional
Controller : Optional
Mixing Box
| Model EKDM |
Rated air flow m3/h | Dimensions (mm) | ||||||||||
| W | H | L | A1 | A2 | B1 | B2 | C | D | E | F | ||
| 306 | 2000 | 1010 | 530 | 3M | 350 | 350 | 300 | 300 | 330 | 115 | 330 | 115 |
| 406 | 3000 | 1010 | 690 | 3M | 500 | 500 | 300 | 300 | 255 | 195 | 255 | 115 |
| 407 | 4000 | 1170 | 690 | 3M | 600 | 600 | 300 | 300 | 285 | 195 | 285 | 115 |
| 408 | 5000 | 1330 | 690 | 3M | 700 | 700 | 300 | 300 | 315 | 195 | 315 | 115 |
| 508 | 6000 | 1330 | 850 | 3M | 700 | 700 | 430 | 430 | 315 | 50 | 315 | 50 |
| 607 | 7000 | 1170 | 1010 | 3M | 600 | 600 | 430 | 430 | 285 | 50 | 285 | 50 |
| 608 | 8000 | 1330 | 1010 | 3M | 800 | 800 | 430 | 430 | 265 | 50 | 265 | 50 |
| 511 | 9000 | 1810 | 850 | 3M | 1000 | 1000 | 430 | 430 | 405 | 50 | 405 | 50 |
| 610 | 10000 | 1650 | 1010 | 3M | 1000 | 1000 | 430 | 430 | 325 | 50 | 325 | 50 |
| 611 | 12000 | 1810 | 1010 | 3M | 1100 | 1100 | 430 | 430 | 355 | 50 | 355 | 50 |
| 712 | 15000 | 1970 | 1170 | 4M | 1100 | 1100 | 590 | 590 | 435 | 50 | 435 | 50 |
| 812 | 18000 | 1970 | 1330 | 4M | 1300 | 1300 | 590 | 590 | 335 | 50 | 335 | 50 |
| 813 | 20000 | 2130 | 1330 | 4M | 1400 | 1400 | 590 | 590 | 365 | 50 | 365 | 50 |
| 915 | 25000 | 2450 | 1490 | 4M | 1500 | 1500 | 750 | 590 | 475 | 50 | 475 | 50 |
| 1015 | 30000 | 2450 | 1650 | 4M | 1600 | 1600 | 750 | 590 | 425 | 50 | 425 | 50 |
| 1313 | 35000 | 2130 | 2130 | 5M | 1300 | 1300 | 1070 | 750 | 415 | 50 | 415 | 50 |
| 1315 | 40000 | 2450 | 2130 | 5M | 1500 | 1500 | 1070 | 750 | 475 | 50 | 475 | 50 |
| 1515 | 45000 | 2450 | 2450 | 6M | 1500 | 1500 | 1230 | 910 | 475 | 50 | 475 | 50 |
| 1417 | 50000 | 2770 | 2290 | 6M | 1700 | 1700 | 1230 | 910 | 535 | 50 | 535 | 50 |
| 1520 | 60000 | 3250 | 2450 | 6M | 2000 | 2000 | 1230 | 910 | 625 | 50 | 625 | 50 |
| 1720 | 70000 | 3250 | 2770 | 7M | 2000 | 2000 | 1550 | 1070 | 625 | 50 | 625 | 50 |
| 1722 | 80000 | 3570 | 2770 | 7M | 2200 | 2200 | 1550 | 1070 | 685 | 50 | 685 | 50 |
| 1626 | 90000 | 4210 | 2610 | 7M | 2600 | 2600 | 1390 | 1070 | 805 | 50 | 805 | 50 |
| 1826 | 100000 | 4210 | 2930 | 7M | 2600 | 2600 | 1710 | 1070 | 805 | 50 | 805 | 50 |
| 1852 | 200000 | 8370 | 2610 | 7M | 5200 | 5200 | 1710 | 1070 | 805 | 50 | 805 | 50 |
| 3652 | 400000 | 8370 | 5910 | 7M | 5200 | 5200 | 3420 | 2140 | 805 | 50 | 805 | 50 |
Note:
■ The width and height for mixing boxes listed above are for units with a 30mm-thick panel. For units with a 50mm-thick panel, the
parameters need a 40mm increase.
■ Standard mixing boxes are equipped with manually-divided multi-leaf hermetic air valves. Electric air valves are also available for auto
control. Air valves are made from zinc-galvanized plates or aluminum alloy with an optional flange.
■ A1 x B1 represents the windward area of return air valve; A2 x B2 represents the windward area of fresh air valve.
■ For total return air, the wind speed at the return air valve is 5~6 m/s; for total fresh air, the wind speed at the fresh air valve is no
larger than 9m/s.
■ The unit height (H) does not include the height of its base.
Specifciations
| Model EKDM |
Rated air flow m3/h | Windward area of coil (m2) | Air flow (m3/h) | Diameter of fan impeller mm | Fan performance | ||||
| 2.25 | 2.50 | 2.75 | 3.00 | Max. total pressure of fan Pa | Max. motor power kW | ||||
| m/s | m/s | m/s | m/s | ||||||
| 306 | 2000 | 0.23 | 1863 | 2070 | 2277 | 2484 | 160 | 1300 | 2.2 |
| 406 | 3000 | 0.34 | 2754 | 3060 | 3366 | 3672 | 200 | 1300 | 3 |
| 407 | 4000 | 0.41 | 3321 | 3690 | 4059 | 4428 | 225 | 1500 | 3 |
| 408 | 5000 | 0.48 | 3888 | 4320 | 4752 | 5184 | 250 | 1800 | 5.5 |
| 508 | 6000 | 0.65 | 5265 | 5850 | 6435 | 7020 | 280 | 1800 | 7.5 |
| 607 | 7000 | 0.69 | 5589 | 6210 | 6831 | 7452 | 280 | 1800 | 7.5 |
| 608 | 8000 | 0.81 | 6561 | 7290 | 8019 | 8748 | 315 | 1800 | 7.5 |
| 511 | 9000 | 0.94 | 7614 | 8460 | 9306 | 10152 | 315 | 1800 | 11 |
| 610 | 10000 | 1.05 | 8505 | 9450 | 10395 | 11340 | 355 | 2000 | 11 |
| 611 | 12000 | 1.17 | 9477 | 10530 | 11583 | 12636 | 400 | 2000 | 15 |
| 712 | 15000 | 1.55 | 12555 | 13950 | 15345 | 16740 | 450 | 2000 | 15 |
| 812 | 18000 | 1.81 | 14661 | 16290 | 17919 | 19548 | 500 | 2000 | 18.5 |
| 813 | 20000 | 1.98 | 16038 | 17820 | 19602 | 21384 | 500 | 2000 | 18.5 |
| 915 | 25000 | 2.66 | 21546 | 23940 | 26334 | 28728 | 560 | 2000 | 22 |
| 1015 | 30000 | 2.99 | 24219 | 26910 | 29601 | 32292 | 630 | 2000 | 30 |
| 1313 | 35000 | 3.40 | 27540 | 30600 | 33660 | 36720 | 630 | 2000 | 30 |
| 1315 | 40000 | 3.99 | 32319 | 35910 | 39501 | 43092 | 710 | 2000 | 30 |
| 1515 | 45000 | 4.65 | 37665 | 41850 | 46035 | 50220 | 800 | 2000 | 37 |
| 1417 | 50000 | 4.95 | 40095 | 44550 | 49005 | 53460 | 800 | 2000 | 45 |
| 1520 | 60000 | 6.36 | 51516 | 57240 | 62964 | 68688 | 900 | 2000 | 45 |
| 1720 | 70000 | 7.27 | 58887 | 65430 | 71973 | 78516 | 900 | 2000 | 55 |
| 1722 | 80000 | 8.05 | 65205 | 72450 | 79695 | 86940 | 1000 | 2000 | 75 |
| 1626 | 90000 | 9.01 | 72981 | 81090 | 89199 | 97308 | 1000 | 2000 | 75 |
| 1826 | 100000 | 10.21 | 82701 | 91890 | 101079 | 110268 | 1120 | 2000 | 110 |
| 1852 | 2000000 | 20.42 | 165402 | 183780 | 202158 | 220536 | 1120x2 | 2000 | 110x2 |
| 3652 | 4000000 | 40.84 | 330804 | 367560 | 404316 | 441072 | 1120x4 | 2000 | 110x4 |
Note:
■ This table only lists some typical models among many models for quick model selection.
■ Total fan pressures listed above are tested on standard fans with rated air flow.
■ External residual pressure = Total fan pressure - Internal resistance. For internal resistance of EKDM units.