Schneider LRD16 Industrial Control Relay TeSys LRD Series For LC1D Contactors
Schneider LRD16 Industrial Control Relay TeSys LRD Series Overload Protection Relay For LC1D Contactors
Application:
TeSys LRD is a flexible range of thermal overload relays from 0.06 kW to 75 kW. Designed for TeSys D contactors ranges, they can be mounted directly under the contactors for compactness or separately using accessories.
TeSys LRD relays are used across industry, infrastructure, building, etc., to provide:
- Protection against motor overload and loss of phase.
- The perfect complement of magnetic only circuit breakers to manage thermal protection for motors.
- Selectable manual, remote or auto reset tripping options for better process management.
Features
TeSys LRD is a reliable series of thermal overload relays designed to cover a range of motor ratings up to 75kW at 400 V. The devices can be combined with TeSys D contactors to form an extremely compact starter.
Specifications:
- Manual or automatic reset
- Sealable flap
- Pre-wiring kit
- Direct mounting with TeSys D contactors
- Terminal block for separate mounting
- Remote electrical reset available as an option
- Connectors: spring terminal, screw clamp, terminal block EverLink (LRD3)
- Class 10 A & 20
Datasheet For reference:
| range |
TeSys
|
|
|---|---|---|
| product name |
TeSys LRD
|
|
| product or component type |
Differential thermal overload relay
|
|
| device short name |
LRD
|
|
| relay application |
Motor protection
|
|
| product compatibility |
LC1D12
LC1D18 LC1D25 LC1D32 LC1D38 |
|
| network type |
AC
DC |
|
| thermal protection adjustment range |
9...13 A
|
|
| [Ui] rated insulation voltage |
600 V power circuit conforming to CSA
600 V power circuit conforming to UL 690 V power circuit conforming to IEC 60947-4-1 |
| network frequency |
0...400 Hz
|
|
|---|---|---|
| mounting support |
Plate with specific accessories
Rail with specific accessories Under contactor |
|
| tripping threshold |
1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
|
|
| [Ith] conventional free air thermal current |
5 A for signalling circuit
|
|
| permissible current |
3 A at 120 V AC-15 for signalling circuit
0.22 A at 125 V DC-13 for signalling circuit |
|
| [Ue] rated operational voltage |
690 V AC 0...400 Hz
|
|
| [Uimp] rated impulse withstand voltage |
6 kV
|
|
| phase failure sensitivity |
Tripping current 130 % of Ir on two phase, the last one at 0
|
|
| control type |
Red push-button stop
Blue push-button for reset mode |
|
| temperature compensation |
-20...60 °C
|
|
| connections - terminals |
Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² flexible without cable end
Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² flexible with cable end Control circuit : screw clamp terminals 2 cable(s) 1...2.5 mm² solid without cable end Power circuit : screw clamp terminals 1 cable(s) 1.5...10 mm² flexible without cable end Power circuit : screw clamp terminals 1 cable(s) 1...4 mm² flexible with cable end Power circuit : screw clamp terminals 1 cable(s) 1...6 mm² solid without cable end |
|
| tightening torque |
Control circuit : 1.7 N.m on screw clamp terminals
Power circuit : 1.7 N.m on screw clamp terminals |
|
| width |
45 mm
|
|
| depth |
70 mm
|
|
| product weight |
0.124 kg
|
Get in Touch