3HP Air Enthalpy Method Calorimeter Testing Laboratory for Air Conditioners and Heat Pumps

 

Overview:

 

The test laboratory can accurately measure the air conditioning cooling capacity, heating capacity, cooling power consumption, heating power consumption, EER, COP, and inverter air conditioner’s rated / maximum / intermediate / minimum cooling capacity, rated / low temperature / intermediate / heating, cooling and heating power consumption, EER, COP, SEER and APF, etc.

 

The test laboratory can test 1~3PH household air conditioners. The test models cover all types of window, split wall mount, split cabinet and split ceiling cassette.

 

The test laboratory uses the air enthalpy method to measure the amount of cooling and heating capacity generated by the measured unit. The laboratory is divided into indoor and outdoor rooms. The indoor room mainly simulates the indoor working condition environment, and the outdoor room mainly simulates the outdoor working condition environment. The outdoor side temperature can be as low as -10 ° C and up to 50 ° C. Can meet the performance testing requirements of household air conditioning.

 

Standards:

 

Design and Testing according to the following standards:

► ISO 5151:2010

► ISO 16358:2013

► Other standards can be customized

 

Types of UUT :

 

- Split wall type

- Split cabinet type

- Split ceiling cassette type

- Window type

- Inverter air conditioner

 

Testing Range:

 

Test range

Cooling capacity

(W)

Heating capacity

(W)

Input power

(W)

Air Flow

(m³/h)

≤7500 ≤9000 ≤8000 200~2000

 

  Indoor Size Dry bulb Temperature Indoor Size Wet bulb Temperature Outdoor Size Dry bulb Temperature Outdoor Size Wet bulb Temperature Power
Control Range 0~50℃ 0~50℃ -10~55℃ 0~55℃(Relative humidity control below 0°C,0~95%RH) 0~8KW
Control Accuracy ±0.2 ±0.2 ±0.2 ±0.2 ±0.5%
Display Accuracy ±0.1 ±0.1 ±0.1 ±0.1 ±0.1%

 

Technical Indicators:

 

Working conditions Indoor side air return condition of /℃ Outdoor side air inlet condition of /℃
Dry bulb temperature Wet bulb temperature Dry bulb temperature Wet bulb temperature
Cooling operation Rated cooling T1 27 19 35 24
T2 21 15 27 19
T3 29 19 46 24
Maximum cooling T1 32 23 43 26
T2 27 19 35 24
T3 32 23 52 31
Freeze-up T1 21 15 21 -
T2 10 -
T3 21 -
Minimum cooling 21 15 Minimum temperature recommended by the manufacturer

Condensation

Condensate removal

27 24 27 24
Heating operation Heat pump rated heating High temperature 20 15(Max.) 7 6
Low temperature 2 1
Extra-low temperature -7 -8
Maximum heating operation 27 - 24 18
Minimum heating operation 20 - -5 -6
Automatic defrost 20 12 2 1
Electric heating rated heating 20 - - -

 

System flowchart:

 

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Sinuo Testing Equipment Co. , Limited
Location Room 101, 1st Floor, No. 6, Third Street, Pingshan Industrial Zone 511495, Shibi Street, Panyu District, Guangzhou, China
Contact Person Zoe Zou

Request A Quote

Please check your email address.
Your message must be at least 20 characters.