SAI143-S33 YOKOGAWA Analog Input I/O Module (For FIO) Safety Control Unit And Safety Node Unit

 


Additional Information:

 

This GS describes the hardware specifications of the analog I/O modules that can be mounted on the safety node unit and the safety control unit.

 

Features
Model SAI143-S33   Analog Input Module(Current output) 4-20 mA,16 channels,module isolateion   
Input impedance during Power-OFF 500 kΩ minimum
Rated accuracy

SAI143-S : ±16 µA (Input range 1 to 23 mA)

SAI143-H : ±16 µA (Input range 0.05 to 23 mA)

External connection

Pressure clamp terminal

MIL cable

Dedicated signal cable

Maximum current consumption

5 V system: 320 mA,

24 V system: 550 mA

2/4-wire setting

Individual channel setting

Changed by setting pins

 


Description:

 

Current Input Module:This module inputs 4 to 20 mA signals from the field. The SAI143 can be made dual redundant.

  • No Zener barriers can be connected to this module. An isolation barrier should be used when an intrinsic safety instrumented system is used.
  • 500 V AC when dedicated signal cable is used.
  • ±32 µA (input range under 0.05 mA) (Style code S3 or later)
  • Rated accuracy of style code S3 or later is ±16 µA (Input range 0.05 to 23 mA).
  • Rated accuracy of style code S2 or earlier is ±16 µA (Input range 1 to 23 mA).
  • When SAI143-S£3 or SAI143-H£C is used in the ambient temperature more than 60°C, number of input channels which a user can use is restricted. Refer to “ProSafe-RS Outline of I/O Modules (for FIO)” (GS 32P06K60-01EN).
  • The maximum voltage drop in the input protection circuit is 0.45 V. The module input impedance varies from 272.5 Ω (20 mA) to 362.5 Ω (4 mA).
  • This function enables to reset the alarm state of Fire and Gas devices by turning off the transmitter power supplied from this module in 2-wire setting. Supported by R4.03.00 or later and style code S4 or later.

 

 

 

Product Details:

 

Brand Name YOKOGAWA
Model SAI143-S33
Condition New
Gross Weight/Shipping Weight 2.2 lbs / 35.2 oz / 1kg
Packing Size 6.4" x 6.4" x 4.8" (16cm x 16 cm x 12 cm)
Country of Origin/Original Country United States (USA)
Lead Time In Stock
Shipping Port Xiamen
Payment T/T
Sales Price Inquiry
Color Depend on product
Warranty 12 months
Lead time 5-8 work days
Courier partners DHL, UPS, TNT, FedEx and EMS
 

 

 

 

 

Datasheet Link:

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company Joyoung International Trading Co.,Ltd
Location Unit 1602, Top Plaza, No.2 Lujiang Road, Siming District, Xiamen Fujian China
Contact Person Candy Wang

Request A Quote

Please check your email address.
Your message must be at least 20 characters.