Product Description
X20SI4100 B&R X20 PLC SYSTEM I/O Module 4 Safe Type A Digital Inputs, 4 Pulse Outputs, 24 VDC
MATERIAL NUMBER:
X20SI4100
DESCRIPTION:
- 4 safe digital inputs
- 4 pulse outputs
- Sink circuit
- Software input filter configurable for each channel
This module is equipped with 4 safe digital inputs. It is designed for a nominal voltage of 24 VDC.
The module can be used to read various digital signals in safety-related applications up to PL e or SIL 3.
The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.
This module is designed for X20 12-pin terminal blocks.
Short description
| I/O module | 4 safe type A digital inputs, 4 pulse outputs, 24 VDC |
General information
| B&R ID code | 0x1DBD |
| System requirements | |
| Automation Studio | 3.0.71 or later |
| Automation Runtime | 2.95 or later |
| SafeDESIGNER | 2.58 or later |
| Safety Release | 1.1 or later |
| mapp Technology Package | mapp Safety 5.7.0 or later |
| Status indicators | I/O function per channel, operating state, module status |
| Diagnostics | |
| Module run/error | Yes, using LED status indicator and software |
| Inputs | Yes, using LED status indicator and software |
| Blackout mode | |
| Scope | Module |
| Function | Module functionality |
| Standalone mode | No |
| Max. I/O cycle time | 800 µs |
| Power consumption | |
| Bus | 0.32 W |
| Internal I/O | 1.25 W |
| Additional power dissipation caused by actuators (resistive) [W] | 0.6 |
| Electrical isolation | |
| Channel - Bus | Yes |
| Channel - Channel | No |
| Certifications | |
| CE | Yes |
| Functional safety | cULus FSPC E361559 Energy and industrial systems Certified for functional safety ANSI UL 1998:2013 |
| Functional safety | IEC 61508:2010, SIL 3 EN 62061:2013, SIL 3 EN ISO 13849-1:2015, Cat. 4 / PL e IEC 61511:2004, SIL 3 |
| Functional safety | EN 50156-1:2004 |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: A(0 - 45°C) Humidity: B(up to 100%) Vibration: A(0.7 g) EMC: B(bridge and open deck) |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| EAC | Yes |
| KC | Yes |
Safety characteristics
| EN ISO 13849-1:2015 | |
| Category | Cat. 3 when using individual input channels, Cat. 4 when using input channel pairs (e.g. SI1 and SI2) or more than 2 input channels |
| PL | PL e |
| DC | >94% |
| MTTFD | 2500 years |
| Mission time | Max. 20 years |
| IEC 61508:2010, IEC 61511:2004, EN 62061:2013 |
|
| SIL CL | SIL 3 |
| SFF | >90% |
| PFH / PFHd | |
| Per channel | <1*10-10 |
| openSAFETY wired | Negligible |
| openSAFETY wireless | <1*10-14* Number of openSAFETY packets per hour |
| PFD | <2*10-5 |
| Proof test interval (PT) | 20 years |
I/O power supply
| Nominal voltage | 24 VDC |
| Voltage range | 24 VDC -15% / +20% |
| Integrated protection | Reverse polarity protection |
Safe digital inputs
| Quantity | 4 |
| Variant | Type A |
| Nominal voltage | 24 VDC |
| Input characteristics per EN 61131-2 | Type 1 |
| Input filter | |
| Hardware | ≤150 μs |
| Software | Configurable between 0 and 500 ms |
| Input circuit | Sink |
| Input voltage | 24 VDC -15% / +20% |
| Input current at 24 VDC | Min. 2 mA to max. 4.59 mA. Hardware revision J0 and later: Min. 2 mA to max. 3.28 mA. |
| Input resistance | Min. 5.23 kΩ, hardware revision J0 and later: Min. 7.33 kΩ |
| Error detection time | 100 ms |
| Insulation voltage between channel and bus | 500 Veff |
| Switching threshold | |
| Low | <5 VDC |
| High | >15 VDC |
| Line length between signal source (pulse output or external signal) and input | Max. 60 m with unshielded line Max. 400 m with shielded line |
Pulse outputs
| Quantity | 4 |
| Variant | Push-Pull |
| Nominal output current | 100 mA, hardware revision J0 and later: 50 mA |
| Output protection | Thermal shutdown of all channels in the event of overload or short circuit, hardware revision J0 and later: Shutdown of individual channels in the event of overload or short circuit |
| Peak short-circuit current | 300 mA, hardware revision J0 and later: 25 A for 15 µs |
| Short-circuit current | 100 mAeff |
| Leakage current when the output is switched off | 0.1 mA |
| RDS(on) | 60 Ω |
| Switching voltage | I/O power supply minus voltage drop due to RDS(on) |
| Total nominal current | 400 mA, hardware revision J0 and later: 200 mA |
Operating conditions
| Mounting orientation | |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | 0 to 2000 m, no limitation |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature | |
| Operation | |
| Horizontal mounting orientation | 0 to 60°C |
| Vertical mounting orientation | 0 to 50°C |
| Derating | See section "Derating". |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Relative humidity | |
| Operation | 5 to 95%, non-condensing |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
Mechanical properties
| Note | Order 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately. |
| Pitch | 25+0.2mm |