Product Description
X20BT9100 B&R X20 PLC SYSTEM Bus Transmitter X2X Link Bus Transmitter With Supply For I/O
MATERIAL NUMBER:
X20BT9100
DESCRIPTION:
- X2X Link bus transmitter
- For seamless expansion of the system
- Up to 100 m segment length
- Supply for internal I/O power supply
- Operation only on the rightmost slot
The bus transmitter is used for seamless expansion of the X20 system. Stations can be up to 100 m apart.
The bus transmitter module is only permitted to be operated with a bus module where the internal I/O power supply is connected through (e.g. X20BM11).
If the supply is used for the internal I/O power supply, this potential group is not permitted to be supplied by any other module. An I/O module with bus module X20BM01 must be used to isolate the potential group.
Short description
| Bus transmitter | X2X Link bus transmitter with supply for I/O |
General information
| B&R ID code | 0x1BC2 |
| Status indicators | X2X bus function, operating state, module status |
| Diagnostics | |
| Module run/error | Yes, using LED status indicator and software |
| X2X bus function | Yes, using LED status indicator |
| Power consumption | |
| Bus | 0.5 W |
| Internal I/O | |
| As bus transmitter | 0.1 W |
| Additionally as supply module | 0.6 W |
| Additional power dissipation caused by actuators (resistive) [W] | - |
| Certifications | |
| CE | Yes |
| UKCA | Yes |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user's manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| EAC | Yes |
| KC | Yes |
Input I/O power supply
| Input voltage | 24 VDC -15% / +20% |
| Fuse | Required line fuse: Max. 10 A, slow-blow |
| Reverse polarity protection | No |
Output I/O power supply
| Nominal output voltage | 24 VDC |
| Behavior on short circuit | Required line fuse |
| Permissible contact load | 10 A |
Operating conditions
| Mounting orientation | |
| Horizontal | Yes |
| Vertical | Yes |
| Installation elevation above sea level | |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
Ambient conditions
| Temperature | |
| Operation | |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | - |
| Storage | -40 to 85°C |
| Transport | -40 to 85°C |
| Relative humidity | |
| Operation | 5 to 95%, non-condensing |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
Mechanical properties
| Note | Order 1x terminal block X20TB06 or X20TB12 separately. Order 1x bus module X20BM11 or X20BM15 separately. |
| Pitch | 12.5+0.2mm |
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Joyoung International Trading Co.,Ltd
Location
Unit 1602, Top Plaza, No.2 Lujiang Road, Siming District, Xiamen Fujian China
Contact Person
Candy Wang