Product Description

High Voltage 6-phase Relay Test System


Model: RELAYSTAR-H60

The RELAYSTAR-H60 is portable 6-phase relay test system for testing most types of modern multi-function protection relays, which can output 6-phase current(6x0…32A) and 4-phase voltage (4x0…300V).

The RELAYSTAR-H60 is an excellent choice when you want higher output voltage(4-phase AC voltage: 4x0…300V, 4-phase DC voltage: 4x0…±300V).

High Voltage 6-phase Relay Test System RELAYSTAR-H60 can be also used as a fault simulator to ensure proper relay configuration for specific applications. This is possible by importing and re-generating transient disturbance files often referred to as COMTRADE files.

 

Main Features

1) 6-phase current(6×32A) + 4-phase voltage(4×300V) output

2) Higher output accuracy(≤0.05% for AC output)

3) End to end test via in-built GPS

4) In-built waveform monitoring and recording

5) Abundant binary inputs and binary outputs

5) Independent Aux. DC supply

6) Powerful RELAYSTAR test software

 

Technical Data

Current Generator

Setting range 6-phase AC(L-N) 6x0…32A
3-phase AC(L-N) 3x0…64A
1-phase AC(LL-LN) 1x0…192A
DC(L-N) 6x0…±15A
Power 6-phase AC(L-N) 6x240VA at 32A
3-phase AC(L-N) 3x400VA at 64A
1-phase AC(LL-LN) 1x750VA at 192A
DC(L-N) 6x240VA at 15A
Accuracy AC: ±2.5mA(≤0.5A), ≤0.05% (0.5~32A)
DC: ≤0.1%
Resolution 1mA

 

Voltage Generator

Setting range 4-phase AC(L-N) 4x0…300V
1-phase AC(L-L) 1x0…600V
DC(L-N) 4x0…±300V
Power 4-phase AC(L-N) 4x80VA at 300V
1-phase AC(L-L) 1x160VA at 600V
DC(L-N) 4x80VA at 300V
Accuracy AC: ±5mV(≤5V), ≤0.05% (5~300V)
DC: ≤0.1%
Resolution 1mV

 

Auxiliary DC Supply

Voltage range 0-300V
Output accuracy ≤0.5%
Power max.160VA

 

Binary Inputs

Number 10
Input characteristics idle contact or potential-free contact
Threshold characteristics “0”:0-6V; “1”:11V-250V
Max. measuring time 999999.999s
Time accuracy ≤0.1ms
Time resolution 0.1ms

 

Binary Outputs

Number 8
Type idle contact
Break capacity 250VAC/0.5A, 250VDC/0.2A

 

DC Voltage Measuring Input

Measuring range 0 ... ±10 V
Accuracy error < 0.02 % rg. typ., < 0.05 % rg. guar.

 

DC Current Measuring Input

Measuring range 0 ... ±20 mA
Accuracy error < 0.02 % rg. typ., < 0.05 % rg. guar.

 

In-built Monitoring and Recording

Monitoring 6-phase current and 4-phase voltage outputs
Recording analog outputs
Mode real time monitoring, no external wiring is required
Recording length unlimited (until the internal memory is full)

 

General Generators

Frequency range: 0~1200Hz
accuracy:<1mHz(0~65Hz),<2mHz(65~450Hz),<5mHz(450~1200Hz)
resolution: 0.001Hz
Phase range: -360° ~+360°
accuracy: 0.1°
resolution: 0. 1°
Harmonic superposition order: 2~24 times
distortion: ≤0.5%

 

Power Supply

Nominal input voltage AC220V/230V±10%, 1-phase
Nominal frequency 50/60 Hz
Rated current 10A at 230V
Connection standard AC socket (IEC 60320)

 

Miscellaneous

Weight 14.8kg(32.63 lb)
Dimensions (W x H x D, without handle) 392x272x237mm(15.43x10.71x9.33 in)
Connection port 1 Ethernet port

 

Environmental Conditions

Operation temperature 0 ... +50 °C (+32 ... +122 °F)
Storage temperature -25 ... +70 °C (-13 ... +158 °F)
Humidity range relative humidity 5 ... 95 %, non-condensing
Vibration IEC 60068-2-6(20m/s2 at 10 ... 150 Hz)

 

High Voltage 6-phase Relay Test System RELAYSTAR-H60 is the portable and reliable tool for engineers to perform protection relay testing in substation.

High Voltage 6-phase Relay Test System RELAYSTAR-H60 can test all types of protection relays virtually according to requirements of ANSI/IEEE.

Get in Touch

Have questions about our products or want to discuss a custom order? Our team is ready to help you.

Company HAOMAI ELECTRIC TEST EQUIPMENT CO.,LTD
Location 806, No.24 Nanlian Road, Nanlian Community, Longgang Street, Longgang District, Shenzhen City, 518116 China
Contact Person William Wang

Request A Quote

Please check your email address.
Your message must be at least 20 characters.