BDV-II 100kv Dielectric Insulating Oil Test Kit Breakdown Voltage Bdv Transformer Oil Tester
Price:
USD1.0
MOQ:
1 set Transformer Oil Tester
Delivery Time:
10 days
Brand:
Delta
Product Description
BDV-II 100kv Dielectric Insulating Oil Test Kit Breakdown Voltage Bdv Transformer Oil Tester
Introduction:
- Bdv-II 100kv Kit Breakdown Voltage Bdv Transformer Oil Tester is developed according to the national standard IEC156 Insulating Oil Dielectric Strength Testing Method ;
- Bdv-II 100kv Kit Breakdown Voltage Bdv Transformer Oil Tester has large LCD display, micro-printer and can store 100 groups data;
- Bdv-II 100kv Kit Breakdown Voltage Bdv Transformer Oil Tester is multi-functional, stable, and easy for operation.
Functions:
- Breakdown test of user-defined
- Proof test
- IEC60156/IS6792/BS5874 test
- ASTM D1816 standard test
- ASTM D877 standard test
- 5 minutes standard test
- Manual test
- Calibration interface for customers
- Uploading data to PC and making word report automatically.
- Result print
Parameters:
| No. | Item Name | BDV-II Breakdown Voltage Bdv Transformer Oil Tester |
| 1 | Output voltage | AC 0V~100KV |
| 2 | Rate of voltage rise | 0.5kv/s±5%, 2kv/s±5%, 3kv/s±5%,5kv/s±5% |
| 3 | Continuously test times | 1 – 9 times |
| 4 | Stir time | 0~999s |
| 5 | Waiting time | 0~999s |
| 6 | Oil temperature measurement range | 0-70℃ |
| 7 | Withstand voltage time | 0-1 min |
| 8 | Ignition arc time | ≤10mS |
| 9 | Test error | 3%RDG+0.3%FS |
| 10 | Display | 256´128 LCD |
| 11 | Data storage | 100 groups of test data |
| 12 | Power supply | AC220V±10%, 50Hz/60Hz |
| 13 | Working environment | 0-50℃, ≤80%RH |
| 14 | Size | 460mm * 380mm * 360mm |
| 15 | Weight | 38kg |
Similar Products
Related Videos
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
Delta Technology (Chongqing) Co., Ltd.
Location
No.85 Zhong Shan Yi Road, Yu Zhong District, Chongqing, China. 400010
Contact Person
Tina Chen