GE IC670MDL740 16-Channel Discrete Output Module with 24 VDC Nominal and Built-in Fuse Protection
Price:
66USD
MOQ:
1
Delivery Time:
2-3 work days
Brand:
General Electric
Product Description

The 12/24 VDC Positive Output Module (IC670MDL740) provides a single group of 16 discrete outputs. The outputs are positive logic or sourcing-type outputs. They switch the loads to the positive side of the DC supply and supply current to the load.
Module Characteristics
| Item | Specification |
|---|---|
| User Input Voltage | 10-30 VDC, 24 VDC nominal, 4A maximum |
| Output Voltage Range | 9.2 VDC to 29.5 VDC |
| Output Current | 0.5 A maximum per point; 4 A maximum per module |
| Outputs per Module | 16 |
| Indicators | Logic-side LEDs indicate on/off status of each output; blown fuse fault and user supply below 9.8 VDC |
| Isolation | 250 VAC continuous, 1500 VAC for 1 minute (User input to logic; user input to frame ground; group to group). No isolation between individual points in a group. |
| Current Drawn from Bus Interface Unit Power Supply | 111 mA maximum |
Output Characteristics
| Item | Specification |
|---|---|
| Inrush Current | 2 A maximum for 100 ms (see Inrush and Steady State Rating diagram) |
| Maximum Load Current (Resistive) | 0.5 A from 10 VDC to 30 VDC |
| Minimum Load Current | 1 mA per point |
| Output Voltage Drop | 0.5 volts maximum |
| Output Leakage Current | 0.5 mA at 30 VDC |
| Response Time - ON | 200 µs max with 0.5 A resistive load |
| Response Time - OFF | 200 µs max with 0.5 A resistive load |
| Protection (Each Output) | Fuse: Metric 5 × 20 mm - 5 A, 250 V, slow-acting, common to all outputs |
After checking the Board ID and verifying that the module is receiving appropriate logic power from the Bus Interface Unit (as indicated by the module's Power LED), the Bus Interface Unit sends output data to the module in serial format. During transmission, the module automatically loops this data back to the Bus Interface Unit for verification. Serial-to-parallel converters then convert this data into the parallel format required by the module. Opto-isolators separate the module's logic components from the field outputs. Power from the external power supply is used to drive the FETs that source current to the loads.
If the module is installed on an I/O Terminal Block with Box Terminals or an I/O Terminal Block with Barrier Terminals, an Auxiliary Terminal Block may be required to provide additional wiring terminals. For the I/O Terminal Block with Wire-to-Board Connectors, external connection points are usually preferred, although an Auxiliary Terminal Block can be used.
Auxiliary Terminal Blocks have all terminals connected together internally. The Auxiliary Terminal Block with box terminals has 13 terminals, each of which accommodates one AWG #14 (approx. 2.1 mm² cross section) to AWG #22 (approx. 0.36 mm² cross section) wire, or two wires up to AWG #18 (approx. 0.86 mm² cross section). The Auxiliary Terminal Block with barrier terminals has nine terminals, each of which can accommodate one or two wires up to AWG #14 (approx. 2.1 mm² cross section).
The following illustration shows how an optional Auxiliary Terminal Block with Box Terminals can be used for power connections when installing this module on an I/O Terminal Block with Box Terminals.
For an I/O Terminal Block with Barrier Terminals or an I/O Terminal Block with Wire-to-Board Connectors, an Auxiliary Terminal Block with Barrier Terminals might be connected as shown in the following example.
Component Focus: GE IC670MDL740
Do you have questions regarding the specifications, warranty, or delivery timeline for this Discrete Output Module?
Skip the general queue. Connect directly with me for a personalized quote and technical confirmation.
Similar Products
Related Videos
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
AMIKON LIMITED
Location
32D units,GuoMao Building No 388 Hubin South Road Siming district Xiamen, Fujian China
Contact Person
Miya