Triconex
3805E Triconex Analog Output Module with 8PT TMR 4-20mA Output and 12-bit Resolution
What is the Tricon? The Tricon is a state-of-the-art controller that provides fault tolerance through Triple-Modular Redundant (TMR) architecture. TMR integrates three isolated, parallel control systems along with extensive diagnostics into a single control system. The system uses two-out-of-three voting to ensure high-integrity, error-free, and uninterrupted process operation with no single point of failure. The Tricon controller operates with three identical channels. Each
16 Bit Resolution AO3481 S2 Triconex Communication Module Safety Instrumented Systems
AO3481 S2 Triconex Communication Module Brand Triconex Product ID AO3481 S2 Packaging Original packaging Warranty period 1 year Delivery time 1-3 days Transportation period DHL /FEDEX /EMS /UPS /TNT Condition 100% original brand Payment method T/T The Triconex AO3481 S2 is a crucial communication module designed for the highly reliable and fault-tolerant Triconex Safety Instrumented Systems (SIS), such as the Tricon system. As part of a system engineered for critical safety
Triconex MP 3101 Main Processor Module with 24 V DC Power and Triple Modular Redundancy
Triconex MP 3101 Main Processor Module Electrical and Operating Profile Nominal supply: 24 V DC Operating range: −15% to +20% (with up to 5% AC ripple) Maximum input tolerance: 33 V DC Reverse voltage protection: down to −0.6 V DC Logic power consumption: ≤ 8 W Short circuit current limit (per input): up to 2.4 A Physical Details Weight: 1.48 kg Estimated dimensions: 4.5 × 18.8 × 21.8 cm The module is built for rack-mounted installation within Triconex systems, not standalone
Triconex 7400208B-020 DI2301 Digital Input Baseplate with 1500V AC/DC Isolation
Triconex 7400208B-020 DI2301 Digital Input Baseplate When engineers research safety PLC, SIS systems, or TMR controllers, they're typically focused on risk reduction rather than feature comparison. This is where Triconex excels. The system's reputation is built on proven performance during years of continuous operation, not marketing claims. Clear, Maintainable Architecture Field engineers consistently note that Triconex systems are straightforward to maintain: Signal paths
Triconex 3008N Main Processor Module with TMR Redundancy for SIS and Emergency Shutdown Systems
Triconex 3008N Main Processor Engineered for critical safety applications, the Triconex 3008N Main Processor is a proven module specified repeatedly in safety projects where stability and reliability are paramount. Originally from Invensys Triconex platforms, this unit is designed for Safety Instrumented Systems (SIS) where uptime and fault tolerance are integral to system design. The 3008N operates within the TMR (Triple Modular Redundant) structure, ensuring system
Bently Nevada 330101-00-20-15-02-05 8 mm Proximity Probe and CSA / ATEX / IECEx Certification
The Bently Nevada 330101-00-20-15-02-05 is a high-performance, non-contacting displacement sensor designed for critical rotating machinery. As part of the gold-standard 3300 XL series, this 8mm probe delivers precision vibration and position data in environments where accuracy isn't optional—it's a safety requirement. Ordering Information Breakdown Engineers and procurement teams often look for specific ordering information strings. Here is the configuration breakdown for
Triconex 7400121-380 External Terminator with 0.15 Ω ±5 % Resistance Snap-fit on Tricon FTP Rail
Triconex 7400121-380 External Terminator Key Features Termination Type: End-of-line, FTP bus Resistance: 0.15 Ω ±5% per channel Temperature Range: -40 to +70 °C Mounting: Snap-fit on Tricon FTP rail Connectors: 16 × rising-clamp terminals Dimensions: 25.2 × 17.8 × 6.5 cm Weight: 1 kg Origin: USA Shipping: Xiamen, China Applications Safety Systems: Triconex SIL 2/3 networks Process Automation: Chemical, petrochemical, oil & gas plants Power Generation: Turbine and generator
Triconex DO2401 7400209-030 Digital Output Baseplate for Redundant Safety Systems
Application Areas Process Automation Systems: Chemical, petrochemical, and power plants System Compatibility Redundant Safety Systems: Works with Triconex 3000/Tricon I/O architecture Functional Benefits Module Replacement & Maintenance: Direct support for DO2401 digital output modules Control Rack Organization: Maintains alignment and stability of output modules When production lines stall, the cost of "Out of Stock" is measured in thousands per hour. Amikon doesn't just
Triconex DI2301 7400208C-020 Baseplate with Rigid Construction, Pre-Drilled Mounting Points
Product Model: DI2301 7400208C-020Manufacturer: TriconexDescription: Baseplate Product Features & Specifications Form Factor & Compatibility Supports DI2301 modules in Triconex 3000/Tricon systems Ensures alignment with adjacent I/O and backplane connections Mechanical Design Rigid construction for vibration and thermal stress resistance Pre-drilled mounting points for precise installation Lightweight, durable material suitable for industrial control environments Electrical &
Triconex 7400221-100 PI2381 Pulse Input Baseplate with 24-bit Counting Resolution
Triconex 7400221-100 PI2381 Pulse Input Baseplate Product Specifications Feature Specification Notes Product Model 7400221-100 PI2381 Pulse Input Baseplate Manufacturer Triconex USA Place of Shipment Xiamen, China - Shipping Size 24.7 × 23 × 6 cm Compact form factor Weight 1.3 kg Easy to install Frequency / Rate Up to 10 kHz High-speed pulse input Voltage Range 5-30 V DC Field-side compatible Counting Resolution 24-bit High-precision counting Frequency Accuracy ±0.01%
Triconex AO3481 Analog Output Module with 12-bit Resolution for Triple Modular Redundancy
Hardware Architecture & Signal Arbitration The AO3481 operates as a 16-point sourcing module (4-20 mA) specifically designed for the Tricon Triple Modular Redundancy (TMR) platform. Its core logic utilizes hardware-level 2-out-of-3 (2oo3) voting to ensure that any single-component failure—whether a DAC drift or microprocessor leg mismatch—is out-voted at the terminal stage. This provides a deterministic command path that prevents uncommanded actuator movement, delivering the
Triconex CM3201 S2 Communication Module with 24 VDC Power Input and IP20 Ingress Protection
Environmental & Electrical Characteristics Power Input: 24 VDC (typical) Operating Temperature: -20°C to 60°C Storage Temperature: -40°C to 85°C Humidity Rating: 10% to 95% RH, non-condensing Ingress Protection: IP20 (typical) Installation & Environmental Guidelines Does the IP20 chassis rating limit our placement within the plant? Yes. The IP20 rating defines the CM3201 S2 as an "open-type" module. It is intended for installation within a secondary NEMA 4 or IP54/65
Triconex 3636R Relay Module with Triple Modular Redundant (TMR) 32 Independent Channels
Technical Specifications Metric Engineering Specification Output Type Electromechanical Relay (Normally Open) Voting Logic Triple Modular Redundant (TMR) - 2oo3 Points 32 Independent Channels Isolation 1500V (Field-to-Logic) On-State Delay
Triconex MP3101 Main Processor Module with SIL3-rated Safety, 24 V DC Power, and TMR Architecture
Technical Specifications Parameter Specification Nominal Input Voltage 24 V DC Operational Voltage Range 24 V DC -15% / +20% + 5% AC ripple Logic Power 8 W maximum Input Voltage 33 V DC Reverse Input Voltage -0.6 V DC Short Circuit Current Limit per Input 2.4 A maximum Safety-Critical Applications The MP3101 is exclusively deployed in SIL3-rated safety loops where "Fail-Safe" is the only acceptable outcome. Emergency Shutdown (ESD): High-speed logic processing for refinery
Triconex 4352B Communication Module with Fiber-Optic Connectivity
For installations using the TCM with fiber connectors (model 4352B), you will need to provide your own fiber-optic cables. The fiber cable you purchase should meet these specifications: Multimode 62.5/125 um cable Maximum length of 1.24 miles (2 kilometers) Compliance with ANSI/TIA/EIA-568-B.3 standards Every Tricon controller requires a Main Chassis and can support up to 14 Expansion or RXM Chassis. At least one ACM, NCM, EICM, or TCM module is necessary for TriStation PC
Triconex 3601E TMR DO Module with 16 Non-Commoned Outputs, Quadruplicated Voter Circuitry
Each Triple Modular Redundancy (TMR) Digital Output (DO) module receives output signals from the Main Processors on each of three channels. These signals are then voted by special quadruplicated output circuitry on the module to produce a single voted output signal for the field termination. This quadruplicated voter circuitry provides multiple redundancy for all critical signal paths, which effectively guarantees high safety standards and maximum system availability during
Triconex 3703E Isolated Analog Input Module with 16 Differential Input Points 12-bit Resolution
Parameter 3703E Voltage 0-5V or 0-10V, + 6% Type TMR, AI No. of Input Points 16, diff, isolated Isolated Points Yes Input Update Rate 50 ms Resolution 12 bits Accuracy < .15% of FSR (0° to 60°C) Input Resistance (load) 30 MΩ (DC), min. Power-Off Resistance 30 MΩ (DC), min. Common Mode Rejection -90 dB @ 60Hz, min. / -100 dB @ DC, min. Common Mode Range ±200V peak Leg-to-Leg Isolation 20 KΩ typical Normal Mode Rejection @ 8Hz: -3 dB / @ 60Hz: -17 dB / @ 120Hz: -23 dB Input
Triconex 8310 Power Supply with 120 VAC/VDC Nominal Voltage for Industrial Safety Systems
Here are the technical specifications for the Power Module 8310. Attribute Specification / Value Chassis Type Main / Expansion / RXM Nominal Voltage 120 VAC / VDC Input VAC @ 47-63 Hz 85-140 VAC Input VDC 95-180 VDC Fuse Rating and Type 5 Amps, time-delay Output Hold Time (nominal to 0 volts) 20 ms minimum Diagnostic Indicators PASS, FAULT, ALARM, TEMP, BAT LOW Core Integration: Universal Chassis Compatibility The Triconex 8310 Power Module serves as the primary energy
Triconex 8312 Power Module with Redundant & Reliable Hot-Swappable Design
Redundant & Reliable Power Design Each Tricon chassis includes two power modules, with either module fully capable of running the system at full load and rated temperature for maximum reliability. Hot-Swappable Operation Power modules are conveniently located on the left side of the chassis and can be replaced while the system remains online, ensuring minimal operational downtime. Power Conversion & Wiring Converts line AC power to DC suitable for all Tricon modules. Terminal
Triconex 4119A Communication Module with 4 Serial Ports, 500 VDC Port Isolation
The 4119A EICM enables seamless communication between your Tricon system and Modbus devices, TriStation, and printers. It supports multiple connection types including RS-232 for point-to-point communication with one master and one slave, or RS-485 for one master and up to 32 slaves. The RS-485 network operates on one or two twisted-pair wires with a range of up to 4,000 feet (1,200 meters). Each EICM features four serial ports and one parallel port, all capable of simultaneou