GE IS200TBAIH1CDC TBAI Analog Input/Output Terminal Board
GE IS200TBAIH1CDC Analog I/O Terminal Board
IS200TBAIH1CDC is a TBAI analog input/output terminal board for documented GE turbine-control I/O arrangements, providing field signal termination and connection to associated analog I/O processing hardware.
01 · Key Features
GE TBAI · ANALOG I/O02 · Core Specifications
ANALOG SIGNAL CHARACTERISTICS| Part Number | IS200TBAIH1CDC |
|---|---|
| Board Type | TBAI Analog Input/Output Terminal Board |
| Analog I/O Capacity | 12 channels total: 10 analog inputs + 2 analog outputs |
| Transmitter Input Span | 1–5 V dc across the documented precision input resistor |
| Typical Input Resistance | 250 Ω |
Show 5 more specifications
| 24 V dc Transmitter Supply | 24 V dc output; documented rating up to 21 mA per channel |
|---|---|
| Maximum Two-Way Lead Resistance | 15 Ω |
| 4–20 mA Output Burden | Up to 800 Ω with the associated PAIC configuration |
| 0–200 mA Output Burden | 50 Ω |
| Output Configuration | One output circuit supports 4–20 mA; the configurable output supports 4–20 mA or 0–200 mA operation. |
03 · Physical & Environmental
BOARD CONSTRUCTION| Operating Temperature | −30 to 65 °C / −22 to 149 °F |
|---|---|
| Board Dimensions | Approximately 10.16 cm wide × 33.02 cm high |
| Technology | Surface mount |
| Terminal Blocks | 2 field-wiring terminal blocks |
| Terminals per Block | 24 |
| System Connection | 3 × DC-37 pin connectors |
04 · Configuration Details
JUMPERS · MONITORING · IDENTIFICATION| Input Selection | Jumper configuration selects current or voltage input arrangements for the documented channels. |
|---|---|
| Return Selection | Jumper positions determine whether the return is connected to common or left open. |
| Input Range Selection | J9A/J10A provide the documented 1 mA or 20 mA selection for the applicable input channels. |
Show 3 more configuration details
| Output Range Selection | J0 selects the configurable output between the documented 20 mA and 200 mA ranges. |
|---|---|
| Output Monitoring | The terminal-board circuit provides a voltage drop across a series resistor for output-current indication. |
| Board Identification | The connector identification device contains terminal-board identification information including serial number, board type, revision and connector location. |
05 · Application
FIELD SIGNAL CONNECTIONTypical application
Used within GE turbine-control I/O arrangements where analog field signals are terminated and routed toward the associated analog I/O processing hardware.
Replacement relevance
The exact board reference becomes important when an analog I/O path, terminal-board assembly, or related control channel requires inspection or replacement.
06 · Wiring & Redundancy
SIMPLEX / TMR| Field Wiring | Input and output wires connect directly to the two I/O terminal blocks on the board. |
|---|---|
| Terminal Capacity | Each terminal block has 24 terminals and the documented installation information specifies wiring up to #12 AWG. |
| Shield Connection | A shield-terminal attachment point is provided adjacent to each terminal block. |
| Simplex | Uses a single TBAI I/O connection. |
| TMR | Uses all three TBAI I/O connections; input signals are distributed to the R, S and T control paths. |
07 · AMIKON Service
INSPECTION · PACKAGING · WARRANTYBefore shipment
AMIKON can arrange product identification and functional inspection before dispatch, with protective packaging for international shipment.
After delivery
12-month warranty. DOA cases should be reported promptly with photos, package/shipping information and the relevant order details.
08 · Contact AMIKON
RFQ / EXACT PART
Let's talk
about your part.
Part number, quantity and delivery requirements are enough to start an inquiry.
09 · Related Models
SELECTED REFERENCESGet in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.