Specifications:
| Nominal Voltage | 2V | |
| Nominal Capacity (C20) | 200Ah (1.80V @ 20℃) | |
| Dimension | Length | 103mm |
| Width | 206mm | |
| Height | 354mm | |
| Total Height | 409mm | |
| Weight(With Electrolyte) | Approx. 17.2 kg | |
| Terminal | M8 | |
| Internal Resistance | Full charged@20℃: 0.0008 Ohm | |
| Max Charging Current | 40A | |
Description:
● Designed life for floating charge is 20 years according to IEC60896-11;
● Rubber separator with floating electrolyte technology;
● High strength ABS material for cover and SAN material transparent container;
● Wide temperature scope of application (-15~45℃);
● Best temperature of application (20±5℃);
● Special filter installation for acid fog proof;
● Transparent container, convenient to observe;
● Super long service life.
Applications:
● Telecommunications
● Cable Television
● Electric Utility
● Alarm & Security system
● UPS
● Control Equipment
● Medical Equipment
● Railroad Utility
● Photovoltaic System
● Alternative Energy System
● High Power Backup Supply
Maintenance
● The battery should be kept clean and dry. Wring tight the acid-proof bolt, and cover it.
● The installation site should be kept clean and dry. With the best temperature about 20 C, the battery room should be given ventilation once weekly.
● No dust falls in the battery.
● Clean the acid-bolt every month with pure water to remove the filth.
Precautions
● The battery pack has high voltage, so direct contact or indirect contact through wet objects with any conducting cable may result in vital injury. The battery pack is energy-storing equipment, so never short-circuit the battery pack during operation and maintenance in any way.
● Do not wear watch, hand chain, bracelet, ring and other conductive objects during operation.
● Only qualified and professional personnel are allowed to install, operate and maintain the equipment.
Tips
● Heat kills batteries. Avoid installation and/or operation in close proximity to heat sources of any kind. While the operating temperature range is -15°C to 45°C, and ideal service life will be realized when the battery is operated in an ambient temperature of 20°C (for cyclic service applications, a range of 5°C to 35°C is recommended).
● If the battery is to be installed in an air or water tight container, ventilation must be provided. Batteries may generate ignitable gases which must not be contained. Because of this, batteries should not be installed near spark producing equipment.
● Avoid installing the battery in an atmosphere where organic solvents or adhesives may be present. Do not clean the battery with oils, thinners or similar substances. Use water only. The case and cover of the battery is ABS plastic resin which may suffer damage from these chemicals.