EJA110E YOKOGAWA Transmitter Differential Pressure transducer EJA110E-JFS5J-917NB
Product Specifications
| Attribute | Value |
|---|---|
| Output signal | 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol) |
| Measurement span (capsule) | 0.5 to 5 kPa (2.0 to 20 inH2O) (For Wetted parts material code S) |
| Process connections | without process connector (1/4 NPT female on the cover flanges) |
| Bolts and nuts material | B7 carbon steel |
| Installation | Horizontal piping and left side high pressure |
| Amplifier housing | Cast aluminum alloy |
| Electrical connection | 1/2 NPT female, two electrical connections and a blind plug |
| Mounting bracket | 304 SST 2-inch pipe mounting, flat type (for horizontal piping) |
EJA110E Differential Pressure Transmitter EJA110E-JFS5J-917NB
Specification Conformance
EJA-E series ensures specification conformance to at least ±3σ.
Reference Accuracy of Calibrated Span
(includes terminal-based linearity, hysteresis, and repeatability)
Measurement Span F
| Parameter | Value |
|---|---|
| Reference accuracy | X ≤ span | ±0.055% of Span X > span | ±(0.005+0.02 URL/span)% of Span |
| X | 2 kPa (8 inH2O) |
| URL (upper range limit) | 5 kPa (20 inH2O) |
Measurement Span M
| Parameter | Value |
|---|---|
| Reference accuracy | X ≤ span | ±0.055% of Span X > span | ±(0.005+0.0025 URL/span)% of Span |
| X | 5 kPa (20 inH2O) |
| URL (upper range limit) | 100 kPa (400 inH2O) |
Measurement Span H
| Parameter | Value |
|---|---|
| Reference accuracy | X ≤ span | ±0.055% of Span X > span | ±(0.005+0.01 URL/span)% of Span |
| X | 100 kPa (400 inH2O) |
| URL (upper range limit) | 500 kPa (2000 inH2O) |
Measurement Span V
| Parameter | Value |
|---|---|
| Reference accuracy | X ≤ span | ±0.055% of Span X > span | ±(0.005+0.005 URL/span)% of Span |
| X | 1.4 MPa (200 psi) |
| URL (upper range limit) | 14 MPa (2000 psi) |
EJA110E Specification Overview
| Measurement Types | |
|---|---|
| Primary Variable | Differential Pressure (DP) |
| Secondary Variable | Static Pressure (SP) |
| Reference Accuracy | |
| Primary Variable | ±0.055% of Span |
| Secondary Variable | ±0.5% of Span available |
| Response Time | |
| Primary Variable | 90 msec |
| Secondary Variable | 360 msec |
| Long Term Stability | |
| Primary Variable | ±0.1% of URL per 10 years |
| Over-pressure Effect | |
| Primary Variable | ±0.03% of URL |
| Rangeability | |
| Primary Variable | 100:1 |
Related Part Numbers
EJA120E-JES4G-912DB EJA120E-JES4J-812EB EJA120E-JES5G-934DJ/KU22/M01/D4/N4 EJA130E-JMS4G-712DD/D4 EJA130E-JMS5J-917DB/C1/X2 EJA130E-JHS4J-817EB/FF1/D4 EJA130E-JHS4J-817EB/FU1/D4 EJA130E-JMS5J-719DC/NS21/N4 EJA130E-EMS5B-99DA/X1/D4/M01/T09 EJA130E-JMS4G-91DDJ/KS21/X2/HC/N4 EJA130E-FHS5G-919DB/X2/D4/M01/T09/KS26 EJA130E-FMS5G-919DB/X2/D4/M01/T09/KS26 EJA130E-JMS5G-719DD/X2/D4/M01/T09/KU22 EJA130E-FMS5G-919DB/X2/D4/M01/T09/KS26 EJA130E-FMS5G-919DB/KS26/X2/D4/M01/T09 EJA210E-JMS4J-912DN-EJ14A2SE01-B EJA210E-JMS5J-912NN-WA13A1SW00-B/D4 EJA210E-DMS4J-912DN-EJ14A2SE01-B/D4 EJA210E-JHS4J-912DN-EA14A1SE01-B/D4