MTL4514D MTL5514D Hazardous Area Switch Proximity Detector Interface
Price:
negotiable
MOQ:
1pc
Delivery Time:
on request
Brand:
MTL
Product Description
MTL4514D – MTL5514D Switch/Proximity Detector Interface for Harsh Environments
Product Specifications
| Attribute | Value |
|---|---|
| Number of channels | One |
| Location of switch | Zone 0, IIC, T6 hazardous area Div.1, Group A, hazardous location |
| Location of proximity detector | Zone 0, IIC, T4–6 hazardous area, if suitably certified Div.1, Group A, hazardous location |
| Hazardous–area inputs | Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR) |
| Voltage applied to sensor | 7 to 9V dc from 1kΩ ±10% |
| Safe-area output | Two, single pole relays with normally-open contact |
Product Description
The MTLx514D enables two safe-area loads to be controlled, through relays, by a proximity detector or switch located in a hazardous area. When selected, open or short circuit conditions in the field wiring are detected by the line fault detect (LFD) facility and indicated on the top of the module. Switches are provided to select phase reversal and to enable the line fault detection.
Relay Characteristics
| Specification | MTL4514D | MTL5514D |
|---|---|---|
| Response time | 10ms maximum | 10ms maximum |
| Contact rating (Safe Area) | 10W, 0.5A, 35V dc | 250V ac, 2A, cosØ >0.7, 40V dc, 2A, resistive load |
| Contact rating (Zone 2) | 10W, 0.5A, 35V dc | 35V, 2A, 100VA |
Similar Products
Related Videos
Get in Touch
Have questions about our products or want to discuss a custom order? Our team is ready to help you.
Company
SC Automation Limited
Location
Unit 1406B 14/F,The Belgian Bank Building, Nos. 721-725 Nathan Road, Mongkok, Kowloon,Hong kong.
Contact Person
Joy chen