| Attribute | Value |
|---|---|
| Number of channels | One |
| Location of switches | Zone 0, IIC, T6 hazardous area Div. 1, Group A hazardous location |
| Location of proximity detectors | Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A hazardous location |
| Safe-area output | Two relays with changeover contacts |
| Hazardous-area input | One input conforming to NAMUR/DIN 19234 standards for proximity detectors |
| Voltage specification | 7.0 to 9.0V from 1kΩ ±10% |
Product Description
The MTL5014 enables two safe-area loads to be controlled by a single switch or proximity detector located in the hazardous area. The safe-area interface has two changeover relays: output 1 and output 2. The output 1 relay reflects the status of the input and may be configured to operate in reverse phase. The output 2 relay may be configured either to repeat (slave) the output 1 relay, or to act as a line integrity monitor. A selectable line-fault-detect (LFD) facility enables an open- or short- circuit fault to be detected in the field wiring.