IEC 60044 Electrical CT Analyzer Current Transformer Test Instrument
Price:
Negotiable
MOQ:
1 Set Current Transformer Test Instrument
Delivery Time:
15 days
Brand:
AI
Product Description
Current Transformer CT Analyzer CT Testing Equipment
Tester for current transformer:
1.Excitation curve and parameters test
2.Turns ratio test
3. Ratio and phase error test
4. Polarity mark check
5. Coil resistance measurement
6. Secondary loop burden measurement
7. Error line curve test for protection CT
8. Transient CT parameters test
9. CT nameplate guess
10.Saturation hysteresis loop curve measurement
2.Turns ratio test
3. Ratio and phase error test
4. Polarity mark check
5. Coil resistance measurement
6. Secondary loop burden measurement
7. Error line curve test for protection CT
8. Transient CT parameters test
9. CT nameplate guess
10.Saturation hysteresis loop curve measurement
Applications of CT Current Transformer Tester:
1 CT nameplate check
2 CT parameters check in work burden
3 CT transient parameters analysis
4 CT ratio and phase error calibration
2 CT parameters check in work burden
3 CT transient parameters analysis
4 CT ratio and phase error calibration
Specifications:
| Item Name | CT Current Transformer Tester | |
| Test standards | IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13 | |
| Power supply | AC220V±10%, 50/60Hz±10% | |
| Voltage output | 0.1~125V (AC) | |
| Current output | 0.001~5A(RMS) | |
| Power output | 300VA | |
| Max. knee voltage measurement | 45KV | |
| Current measurement | Range | 0~10A (automatically change range in 0.1/0.4/2/10A) |
| Error | <±0.1%+0.01%FS | |
| Voltage measurement | Range | 0~200V (automatically change range in 1V/10V/70V/200V) | |
| Error | < ±0.1%+0.01%FS | ||
| Turns ratio measurement Range | 1~35000 1~2000, error<0.05% 2000~5000,error<0.1% 5000~35000,error<0.2% |
||
| Phase measurement | error | ±2min | |
| resolution | 0.01min | ||
| Coil resistance measurement | Range | 0~80Ω (automatically change range in 2ohm/20ohm/80ohm) | |
| Error | < 0.2%RDG+0.02%FS | ||
| Maximum resolution : 0.1mΩ | |||
| Temperature measurement | -50~100 Celsius degree; error<3 Celsius degree | ||
| CT Secondary burden | Range | 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) | |
| Error | <0.2%RDG+0.02%FS | ||
| Maximum resolution : 0.001ohm | |||
| Memory capacity | >1000 groups test results | ||
| Working condition temperature | -10℃~50℃; moist ≤90% |
||